Permissible wire
bundling
Table 2-3 shows which wire functions should be bundled together.
NOTE
For installation where high EMI/RFI noise cannot be avoided, we
recommend you use shielded twisted pair wires for the signals in bundle 2.
Table 2-3 Permissible Wiring Bundling
Bundle No. Wire Functions
1 Line power wiring
Earth ground wiring
Control relay output wiring
Line voltage alarm wiring
2 Analog signal wire, such as:
Input signal wire (thermocouple, 4 to 20 mA, etc.)
4-20 mA output signal wiring
Slidewire feedback circuit wiring
Digital input signals
Communications
3 Low voltage alarm relay output wiring
Low voltage wiring to solid state type control circuits
Identify your wiring
requirements
To determine the appropriate diagrams for wiring your controller, refer to
the model number interpretation in this section. The model number of the
controller can be found on the inside of the case.