User Guide

TStatSpec
TM
26
OUTPUTS
This section allows user to configure the outputs.
Heat Stages:
Cool Stages:
These fields allows user to configure the number of heat
stages and cool stages for the application the subbase is
being used for.
The following table explains the use of the relays in different
subbases.
Outputs Model Equipment
type
Default value number of stages available for configuration
Heat Stages
T7350A,
1H1C
Standard One Stage None
One Stage
Two Stage
T7350B,
2H2C
Standard Two Stage None
One Stage
Two Stage
Three Stage
T7350D,
3H3C, RH
&
T7350H,
3H3C, Com
Standard Three Stage None
One Stage
Two Stage
Three Stage( Not available if configured for 4
stages of cooling)
T7350M,
Mod
&
T7350H,
Mod, Com
Standard Heat Enable Heat Enable()
One Stage
Two Stage (Used as auxiliary relay or second
stage of heat or cool relay. Not available if used as
second stage of cooling)
Aux Heat Stages
T7350A,
1H1C
Heat Pump One Stage None
One Stage
T7350B,
2H2C
Heat Pump Two Stage None
One Stage
Two Stage
T7350D,
3H3C, RH
&
T7350H,
3H3C, Com
Heat Pump One Stage None( No auxiliary heating)
One Stage (of auxiliary heat)
Two Stage(of auxiliary heat )