The following section details each field in this screen:
KeyPad Lockout:
This option allows the user to configure the keypad lockout
enable/disable through special keypad sequence on the
thermostat.
Enable All: Selecting this option will allow the user to access
any keys on the thermostat. No lockout will be imposed.
Enable Setpoints & Override: This option will lockout all
keys except Temporary Occupied, Temporary Not Occupied,
Increase, Decrease, and Information.
Info Key Only: This option will lockout all keys except the
information key.
Display Units:
This option allows the user to configure the display units in the
thermostat for temperature fields.
Degrees F: Select this option to set the display unit for
temperature fields as degree Fahrenheit.
Degrees C: Select this option to set the display unit for
temperature fields as degree Centigrade.
Clock Display:
This option allows the user to configure the display mode of
time in the thermostat.
12 Hour(AM/PM): Selecting this option will display the
thermostat time in 12 hour format.
24 Hour: Selecting this option will display the thermostat time
in 24 hour format.
System Switch:
This option allows the user to configure the system operation
of the thermostat.
OFF: When this option is selected, heat and cool states are
disabled.
AUTO: The thermostat is configured for Automatic
Changeover. When this option is selected, heating and
cooling stages are enabled to maintain heating and cooling
setpoints.
Cool: When this option is selected, cooling stage operates on
call for cooling. Heating stages are disabled.
Heat: When this option is selected, heating stage operates on
call for heating. Cooling stages are disabled.
Emergency Heat: This option is available only when the
equipment type is selected as Heat Pump. Auxiliary heat
serves as stage one. Compressor stages are locked off.
Fan Switch:
This option allows the selection of fan switch.
ON(On in Occupied): When this option is selected, fan
operates continuously in scheduled occupied and stand by
periods and bypass mode. Fan cycles with call for heating or
cooling during unoccupied periods.
AUTO(Intermittent in Occupied): When this option is
selected, fan cycles with call for heating or cooling during
scheduled occupied, standby and unoccupied periods.
If the T7350 is scheduled for occupied and occupancy sensor
is unoccupied(thus effective occupancy is standby), then the
fan is off and will turn on with a call for heating and cooling.
This applies to both On and Auto. This follows the action of
the auxiliary relay when configured for TOD. This is further
modified by the selection of conventional(OFF with Heat) or
electric heat(ON with Heat).
Configuring SetPointPage
Description:
The Setpoints page allows the user to configure the heating
and cooling setpoints, energy management features,
dehumidification features, recovery setpoints and bypass
timer.