User Guide

TStatSpec
TM
31
Procedure:
Click the T7350 thermostat controller in the workspace to
open the configuration dialog box. Choose the Setpoints
screen, if not already displayed.
Fig. 28. Configuration Screen
The following section describes each field in this screen:
Heating and Cooling setpoints: This section allows user to
specify the heating and cooling setpoints.
The following table gives the default value for each setpoint
and its valid range.
Setpoint Default value Min. and Max.
ranges
Description
Cool Unoccupied Stpt 85 degF
or
29 degC
45-99 deg F
or
7-37 deg C
Unoccupied cooling setpoint
Display resolution: 1 deg F/deg C.
Unoccupied Cool >= Occupied Cool >= Occupied
Heat +2 deg F ( 1 deg C)
Unoccupied Cool >= Standby Cool >= Standby Heat
+2 deg F ( 1 deg C)
Cool Standby Stpt 78 deg F
or
26 deg C
45-99 deg F
or
7-37 deg C
Standby cooling setpoint
Display resolution: 1 deg F/deg C.
Unoccupied Cool >= Standby Cool >= Standby Heat
+2 deg F ( 1 deg C)
Cool Occupied Stpt 78 deg F
or
26 deg C
45-99 deg F
or
7-37 deg C
Occupied cooling setpoint
Display resolution: 1 deg F/deg C.
Unoccupied Cool >= Occupied Cool >= Occupied
Heat +2 deg F ( 1 deg C)
Max Occupied Cool >= Occupied Cool >= Occupied Heat +2
deg F( 1 deg C)
Heat Occupied Stpt 70 deg F
or
21 deg C
40-90 deg F
or
4 -32 deg C
Occupied heating setpoint
Display resolution: 1 deg F/deg C.
Unoccupied Heat <= Occupied Heat <= Occupied Cool -2
def ( 1 deg C)
Min Occupied Heat <= Occupied Heat <= Occupied Cool -2
deg F( 1 deg C)