UV100A Product Data

UV100A ULTRAVIOLET SYSTEMS
68-0248—4 2
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
SPECIFICATIONS
IMPORTANT
The specifications in this publication do not include
normal manufacturing tolerances; therefore, an
individual unit may not exactly match the listed
specifications. This product is tested and calibrated
under closely controlled conditions and some minor
differences in performance can be expected if those
conditions are changed.
TRADELINE® Models available:
The UV100A Ultraviolet System is available in four models: a
single-lamp air treatment system; a dual-lamp air treatment
system; a 120V surface treatment system; and a 240V
surface treatment system.
UV100A Air Treatment System (single-lamp) is mounted in
the return air duct of an HVAC system. It has moderate-
efficiency performance against airborne bacteria in return
air applications.
UV100A AIr Treatment System (dual-lamp) is mounted in
the return air duct of an HVAC system. It has high-
efficiency performance against airborne bacteria in return
air applications.
UV100A Surface Treatment System (120V or 240V) is
mounted downstream from air conditioner cooling coils of
HVAC system. The unit reduces mold growth and spores
on duct surfaces, coils and drip pans. (Optionally, UV100A
Surface Treatment System can be mounted in return air
duct of HVAC system. It has moderate efficiency per-
forming against airborne bacteria in return air applications.)
Efficiencies:
UV100A Surface Treatment System (120V and 240V): Kills
up to 99.9% of mold on system cooling coils or kills up to
75% of airborne bacteria passing by the system
(depending on installation).
Test performed in a test duct showed reduction in
colony-forming aspergillus niger mold spores when
surface was irradiated at a distance of 18 in. for three
hours in still air, using new lamps.
Test showed single-pass kill-rate of serratia bacteria in
a clean metal 12 in. x 25 in. duct at an airflow of
2000 cfm using new lamps.
UV100A Air Treatment System (dual-lamp): Kills up to 87%
of airborne bacteria passing by the system.
Test showed single-pass kill-rate of serratia
marcescens bacteria in a clean metal 12 in. x 25 in.
duct at an airflow rate of 2000 cfm using new lamps.
UV100A Air Treatment System (single lamp): Kills up to
70% of airborne bacteria passing by the system.
Test showed single-pass kill-rate of serratia
marcescens bacteria in a clean metal 12 in. x 25 in.
duct at an airflow rate of 2000 cfm using new lamps.
Electrical Ratings:
Power Rating: 120 Vac, 60 Hz or 240V, 60 Hz.
Consumption:
Temperature Ratings:
Air Treatment System (dual lamp):
Ambient Temperature Range: 30°F to 104°F (-2°C to
40°C).
Lamp Temperature Range: 30°F to 104°F (-2°C to 40°C)
and 170°F (77°C) in moving air.
Air Treatment System (single lamp) and Surface Treatment
System:
Ambient Temperature Range: 30°F to 120°F (-2°C to 49°C)
and 170°F (77°C) in moving air.
Lamp Temperature Range: 30°F to 120°F (-2°C to 49°C)
and 170°F (77°C) in moving air.
Relative Humidity:
Up to 95% rh, non-condensing.
Dimensions: See Fig. 3.
Approvals:
Underwriters Laboratories: File no. E223009
The health aspects associated with the use of this product and
its ability to aid in disinfection of environmental air have not
been investigated by UL.
Model
Voltage
(Vac)
Input
Power
(A)
Bulb
Wattage
(W)
UV100A1000 Air Treatment
System (single lamp)
120 0.4 18
UV100A1018 Air Treatment
System (dual lamp)
120 0.7 36
(each bulb)
UV100A1059 Surface
Treatment System (120V)
120 0.85 36
UV100A2008 Surface
Treatment System (240V)
240 0.35 36