User Guide

UV100E ULTRAVIOLET SYSTEM
69-1573—3 10
9. Reconnect power to your UV System.
10. For UV Air Treatment Systems, wait ten minutes for the airflow sensor to
calibrate. During this time, the furnace fan must remain off.
NOTE: Failure to wait ten minutes for the airflow sensor to calibrate before powering
the system fan causes the airflow sensor to incorrectly calibrate and the
device to incorrectly function. If this occurs, remove power to the furnace or
turn off the system fan, wait ten minutes, and then resume normal fan
operation.
11. Verify that your ultraviolet bulb is operating by viewing only through the lamp
light indicator on the lamp handle. Never look directly at your bulb while
it is illuminated.
12. Reconnect power to your heating and cooling system.
Bulb Replacement
Replacement of the bulb in your ultraviolet lamp when the LED is solidly lighted is
required to maintain effectiveness.
1. Obtain the correct replacement bulb/handle assembly or replacement bulb for
your unit. See Table 1.
2. Disconnect the power to your heating and cooling system.
3. Unplug or turn off power to your UV System and allow the bulb to cool for at least
15 minutes.
4. Rotate the lamp handle counterclockwise and gently pull the lamp handle to
remove the bulb. See Fig. 5.
Table 1. Select a Replacement Bulb/Handle Assembly or Replacement Bulb.
Unit Description
Replacement Bulb/
Handle Assembly
SnapLamp™
Replacement Bulb
UV100E1043
Air Treatment System
UC100E1006 UC18W1004
UV100E2009
Air Treatment System
UC100E1030
(two needed)
UC36W1006
(two needed)
UV100E3007
Surface Treatment System
UC100E1030 UC36W1006