V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR
60-2309—11 2
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
SPECIFICATIONS
Models:
V4055A Actuator, with V5055, V5097 or VE5000 Gas Valves,
provides on-off control of fuel. With proper adapter (see
Accessories), it replaces the V4034 Actuator on a V5034
Gas Valve.
V4055B Actuator is a high pressure version of V4055A.
V4055D Actuator is identical to V4055A, except has a
Proof-of-Closure Switch. Used with V5055C/V5097C
(double seal) for valve seal overtravel interlock.
V4055E Actuator is identical to V4055B, except has a
Proof-of-Closure Switch. Used with V5055E/V5097E
(double seal) for valve seal overtravel interlock.
NEMA 4 weatherproof models available.
Nominal Opening Time: See Table 1.
Table 1. Nominal Opening Time (seconds).
Maximum Closing Time: One second when de-energized.
Ambient Operating Temperature Ratings:
60 Hz Models: -40°F to +150°F (-40°C to +66°C).
50 Hz, 50/60 Hz Models: -10°F to +158°F (-23°C to +70°C).
Mounting: V4055 Actuator attaches directly to V5055/V5097
Valve with two sets of screws positioned 90 degrees apart.
Combination is multipoise.
NOTE: 220 to 240 Vac, 50/60 Hz models are vertical mount
only.
Pressure Ratings: See Table 2.
Table 2. Pressure Ratings of Valve-Actuator Combinations.
a
Use a V4055D or V4055E (with Proof-of-Closure Switch) with a V5055/V5097C or V5055/V5097E (with double seal) for valve
seal overtravel interlock.
b
Maximum operating pressure differential.
c
Maximum closeoff pressure without seat leakage. This is the maximum valve pressure drop allowed while fully closed, and is
independent of the valve body rating.
Electrical Ratings: See Tables 3 and 4.
Model 50 Hz 60 Hz
Standard 32 26
Fast-opening 16 13
Valve
Actuator
V4055A,D
a
V4055B,E
a
Differential
b
Closeoff
c
Differential
b
Closeoff
c
psi mbar psi bar psi mbar psi bar
V5055/V5097A,C: 3/4 to 3 in. 5 340 15 1 15 1000 15 1
V5055A,C: 4 in. 3 200 15 1 5 340 15 1
V5055/V5097B: 3/4 to 3 in. 5 340 15 1 15 1000 15 1
V5055B: 4 in. 3 200 15 1 5 340 15 1
V5055/V5097D,E: 3/4, 1-1/4, 1-1/2 in. 5 340 75 5 25 1700 75 5
V5055/V5097D,e: 2, 2-1/2, 3 in. 5 340 45 3 15 1000 45 3