User Guide

V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR
60-2099—10 2
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
SPECIFICATIONS
IMPORTANT:
The specifications given in this publication do not
include normal manufacturing tolerances. Therefore,
this unit may not exactly match the listed
specifications. Also, this product is tested and
calibrated under closely controlled conditions, and
some minor differences in performance can be
expected if those conditions are changed.
Models:
V4062A HI-LO-OFF Gas Valve Actuator.
V4062B HI-LO-OFF Gas Valve Actuator, high pressure.
V4062D HI-LO-OFF Gas Valve Actuator with proof-of-closure
switch. Use with V5055/V5097C,E (double seal) gas
valves for valve seal overtravel interlock. Do not use V4062
with V5034 Valve body.
Electrical Ratings:
Standard V4062A,D Actuators (Table 1):
60 Hz, 26 second opening.
50 Hz, 32 second opening.
Table 1. Standard V4062A,D Actuators.
Fast-opening V4062A,D Actuators (Table 2):
60 Hz, 13 second opening.
50 Hz, 16 second opening.
Table 2. Fast-opening V4062A,D Actuators.
a
230V, 50 Hz power supply.
b
230V, 60 Hz power supply.
Fast-opening V4062B Actuators (Table 3):
60 Hz, 13 second opening.
50 Hz, 16 second opening.
Table 3. Fast-opening V4062B Actuators.
a
230V, 50 Hz power supply.
b
230V, 60 Hz power supply.
Pressure Ratings Of Valve-Actuator Combinations:
See Table 4.
Auxiliary Switch And Proof-Of-Closure Switch Ratings:
See Table 5.
Table 4. Pressure Ratings of Valve-Actuators Combinations.
a
Use a V4062D (with proof-of-closure switch) with a V5055/V5097C or E (with double seal) for valve seal overtravel interlock.
b
Maximum operating pressure differential.
c
Maximum closeoff pressure without seal leakage. This is the maximum allowable pressure drop to which a valve may be
subjected when fully closed, and is independent of the valve body rating.
Voltage/
Frequency
Opening Holding
WVAWVA
120V/60 Hz 59.5 129 19.0 28.0
100V/50-60 Hz 53.0/42.7 105/80 20.0/17.2 33/29
200V/50-60 Hz 72.01/52.5 160/110 18.4/16.2 28/24
Voltage/Frequency
Opening Holding
WVAWVA
120V/60 Hz 59.5 129 19.0 28.0
220V/50 Hz 84.0 196 17.0 27.0
220V/50 Hz 82.0 180 16.5 26.4
220V-240V; 50-60 Hz
a
74.5 143.5 13.7 24.8
220V-240V; 50-60 Hz
b
61.9 112 11.2 20.5
Voltage/Frequency
Opening Holding
WVAWVA
220V-240V; 50-60 Hz
a
76.5 150.6 13.3 28.8
220V-240V; 50-60 Hz
b
64.4 118.2 11 23.2
Valve
V4062A,D Actuator
a
V4062B Actuator
Differential
b
Closeoff
c
Differential
b
Closeoff
c
psi mbar psi bar psi mbar psi bar
V5055A,C; V5097A,C 3/4 to 3 in. 5 340 15 1 15 1000 15 1
V5055A,C 4 in. 3 200 15 1 5 340 15 1
V5055B, V5097B 3/4 to 3 in. 5 340 15 1 15 1000 15 1
V5055B 4 in. 3200515340151
V5055D,E, 3/4, 1, 1-1/4, 1-1/2; V5097D 3/4 in. to 2 in. 5 340 75 5 25 1700 75 5
V5055D,E; V5097D,E 2, 2-1/2, 3 in. 5 340 45 3 15 1000 45 3