Submittal Sheet

3
77-5315-1
V5011A, B, D-H, J SINGLE SEATED VALVES
Table 1. V5011 Model Descriptions and Body Specifications.
Fig. 2. Valve Pressure-Temperature Ratings.
NOTES:
1. For high fluid temperatures, the valve and/or
piping should be insulated to prevent ambient
temperature from exceeding actuator ratings.
2. Maximum temperature differential in alternate
hot and cold water use, 140F (60C).
V5011A Equal
Percentage
V5011D Equal
Percentage
V5011A Equal
Percentage
V5011B Equal
Percentage
V5011D Equal
Percentage
V5011E Equal
Percentage
Flanged
Flanged
2-1/2 or 3
4, 5, or 6
Direct
Direct
Direct
Reverse
Reverse
100; 3 in.
63; 2-1/2 in.
160; 4 in.
250; 5 in.
360; 6 in.
ANSI
Body
Class
250
125
125
250
150
Model and Plug
Characteristic
End
Connections
Body
Size in
Inches
Capacity
Index (C )†
v
Action*
V5011F Equal
Percentage,
V5011G Linear
Screwed NPTDirect
V5011H Equal
Percentage,
V5011J Linear
Reverse Screwed NPT
2
2-1/2
3
1-1/2§
1/2§
3/4§
1
1-1/4§
1/2
3/4
1
1-1/4
40
63
100
0.4, 0.63, 1.0,
1.6, 2.5, 4.0
6.3
10.0
16
25
2.5, 4.0
6.3
10.0
16
150
0.4 C available only on V5011G
v
Direct: stem down to close.
Reverse: stem up to close.
*
§
Also available with metal-to-metal seating.
§
260
(1713)
FLUID TEMPERATURE F(C)
(INCLUDES BODY, DISC AND PACKING LIMITATIONS)
240
(1655)
220
(1517)
200
(1379)
180
(1241)
160
(1103)
140
(965)
120
(827)
100
(689)
80
(552)
60
(414)
40
(226)
20
(138)
50
(10)
75
(24)
100
(38)
125
(52)
150
(66)
175
(79)
200
(93)
225
(107)
250
(121)
275
(135)
300
(149)
325
(163)
350
(177)
0
V5011 TWO-WAY VALVE COMPOSITE RATINGS
V5011 A & B
(WATER)
V5011 F& H
(WATER)
217(PSI)
V5011 D&E
(WATER)
V5011 G&J
(STEAM)
C7974-1
FLUID PRESSURE PSI (kPa)