INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
IMPORTANT
Install the valve so the fluid flows in the direction of
the arrow cast on the body. Mount the valve with the
operator motor shaft horizontal.
Location
In selecting a location, the following must be considered.
1. Make sure sufficient space has been provided for the
complete valve assembly. The actuator assembly fits
over the valve stem.
2. The actuator assembly should not be mounted below
the valve where moisture or dirt may accumulate.
The ambient temperature must not exceed the maximum
limits for the valve or motor. Controlled liquid-pressure must
not exceed the maximum pressure limits of the valve.
Piping Hookups
All piping must comply with local codes and ordinances. Refer
to Fig. 4-8 for typical piping hookups.
Fig. 3. Valve pressure-temperature ratings.
260
(1713)
FLUID TEMPERATURE
°
F(
°
C)
(INCLUDES BODY AND PACKING LIMITATIONS)
240
(1655)
220
(1517)
200
(1379)
180
(1241)
160
(1103)
140
(965)
120
(827)
100
(689)
80
(552)
60
(414)
40
(226)
20
(138)
50
(10)
75
(24)
100
(38)
125
(52)
150
(66)
175
(79)
200
(93)
225
(107)
250
(121)
275
(135)
300
(149)
0
FLUID PRESSURE PSI (kPa)
V5013 B & C
V5013F
217(PSI)
M11756
Fig. 4. Typical V5013F or B mixing valve with
constant volume through coil.
Fig. 5. Single zone bypass for reset control.
COIL
RETURN
SUPPLY
PUMP
PULL
PUMP
AB
A
B
BYPASS
BOILER
V5013F OR B
M11757
PUMP
AB
A
B
BYPASS
BOILER
V5013F OR B
M11758
MIXED
DISCHARGE
WATER TO
HEAT LOAD
Fig. 6. V5013C diverting valve used to
change over complete system.
RETURN
PUMP
BOILERCHILLER
AB
A
B
V5013C