VR4300 Continuous Pilot Dual Automatic Valve Combination Gas Control
Combination gas control for use in 120 Vac, gas-fired, standing
pilot appliances with capacities from 30 to 300 cfh.
Control includes safety shutoff, manual valve, two automatic
operators, pressure regulator and pilot adjustment.
Compact size.
Provides two automatic valves.
Solenoid operated first automatic valve opens on thermostat call for
heat, closes when call for heat ends.
Diaphragm-operated second automatic valve opens under control of
regulator; closes if gas or power supply is interrupted.
Meets codes requiring dual safety shut-off.
Natural to LP and LP to Natural conversion kits available for
standard and slow opening gas valves.
All adjustments, wiring connections and pilot outlet are accessible
from top of control.
Adjustable servo regulator effectively maintains almost constant gas
output pressure under wide fluctuations in gas supply pressure.
Compatible with ECO connector.
LITE-RITE (OFF-PILOT-ON) lighting sequence.
Wiring connections for 120 volt control Type: Single Stage
Body Pattern: Straight-through with flange
Capacity @ 1 in. p.d. 300,000 BTU/hr; 30,000 BTU/hr minimum
Anticipator Setting: 0.13 A
Ignition Type: Standing Pilot
Ambient Temperature Range: 0 F to 175 F (-18 C to +79 C)
Pressure Ratings: 1/2 psi (3.5 kPa)
Pressure Tapping: 1/8 in. NPT with plug
Electrical Ratings: 120 Vac
Frequency: 60 Hz
Pilot Gas Outlet: Compression fitting for 1/4 in. OD tubing
Electrical Connections: 1/4 in. male quick connects; 24 in. (610 mm)
leadwire.
Mounting: 0 to 90 degrees in any direction from the upright position of
the gas control knob, including vertically.
Includes: One 1/2 in. x 3/8 in. reducer bushing, Two 3/4 x 1/2 in.
reducer bushings, 393691 Natural to LP gas conversion kit.
Approvals:
American Gas Association: AGA Design Certified: File No. L2025006;
CGA Design Certified: File No. L2025006
120V
THERMOSTAT
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
DO NOT JUMPER THESE TERMINALS. THIS
SHORTS VALVE COIL AND MAY BURN OUT
ANTICIPATOR IN THERMOSTAT.
OPTIONAL HIGH LIMIT.
L1
(HOT)
L2
HIGH LIMIT
CONTROLLER
M3092B
GAS CONTROL
TERMINALS
L2
L1
1
1
2
2
3
3
Product Number Type of Gas
Opening Characteristics
(standard, step) Inlet/Outlet Size (in.)
Pressure Regulator Setting
Electrical
Ratings(psi) (kPa)
* VR4300A4502 Natural Standard 3/4 in. x 3/4 in. 3.5 in. wc 0.87 kPa 120 Vac
* TRADELINE models • SUPER TRADELINE models