Submittal Sheet

SPECIFICATION DATA
65-0053-1
® U.S. Registered Trademark
Copyright © 2002 Honeywell • All Rights Reserved
V48A,F,J; V88A,J
Diaphragm Gas Valves
APPLICATION
The V48 and V88 are solenoid-operated diaphragm valves
suitable for LP (Liquefied Petroleum), natural, and
manufactured gases. They are normally used on atmospheric
boilers, commercial water heaters, and rooftop heaters.
SPECIFICATIONS
Models:
V48A (120 Vac) or V88A (24 Vac) solenoid operated
diaphragm valves for 1/2 or 1 psi (3.4 or 6.9 kPa) maximum
operating pressure.
V48F (120 Vac) solenoid operated diaphragm valve for 5 psi
(34.5 kPa) maximum operating pressure.
V48J (120 Vac) or V88J (24 Vac) solenoid operated
diaphragm valves for 1 psi (6.9 kPa) operating pressure
and 150°F (66°C) maximum ambient temperature.
Type of Gas: Suitable for liquefied petroleum (LP), natural,
manufactured, and sulfur-bearing gases.
Valve Capacity: See table in Fig. 2.
FEATURES
Line voltage, 2-wire thermostat or controller used with
a V48; V88 used with 24V thermostat.
Valves provide slow opening and fast closing.
Two second maximum closing time.
V48J, V88J rated for 150°F (66°C) ambient temperature.
V48F rated for 5 psi (lb. per sq. in.) (34.5 kPa). V48A
and V88A rated for either 1/2 or 1 psi (3.4 or 6.9 kPa),
depending on model. V48J and V88J rated for 1 psi
(6.9 kPa).
One model for natural and LP gases.
Wide range of sizes and capacities.
Firm closing; diaphragm is both weight and spring
loaded.
Valve closes on power failure; recommended for final
shutoff service.
Adjustable or fixed bleed orifices available for
installation by OEM.
Valve position indicator on 1-1/4 in. V48A2227 and 2 in.
V48F1103 Valves.
Valve Pattern: Straight-through, non-offset.
Valve Body Material: Die-cast aluminum.
Pilot Tapping (see Table 1 for thread type):
3/4 through 1-1/2 inch valves: 1/8-27 NPT or 1/8-28 BSP.PI.
2 through 3 inch valves: 1/4-18 NPT.
Bleed Tapping (see Table 2 for thread type): 1/8-27 NPT or
1/8-28 BSP.PI.
Valve Opening Time:
Five seconds maximum at 2 oz/in.
2
(0.86 kPa) pressure.
Adjustable bleed valve assembly or fixed bleed orifices
available for longer opening time (NPT threads only; see
Accessories).

Summary of content (4 pages)