Install Instructions

VBN THREADED CONTROL BALL VALVES AND ACTUATORS
5 62-2025EFS—06
Fig. 10. MVN613 with Floating Control.
Fig. 11. MVN613 or MVN643 with Two Position SPDT
Control.
Fig. 12. MVN643 with Two Position SPST Control.
Fig. 13. MVN713 with 4-20mA Control.
Fig. 14. MVN713 with 0(2)-10 Vdc Control.
FLOATING ACTUATOR
24 VAC
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FLOATING
CONTROLLER
M33137D
2
3
4
1
BLACK
WHITE
BROWN
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
USE CLASS II 24V TRANSFORMER FOR MVN643.
2
FLOATING ACTUATOR
24 VAC
1
CONTROLLER
2
3
4
1
M33138C
BLACK
WHITE
BROWN
2
M33557C
FLOATING ACTUATOR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
3
4
1
24 VAC
BLACK
BROWN
WHITE
SPST
PROPORTIONAL ACTUATOR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
4-20mA
CONTROLLER
M33141C
1
2
3
+
+
DIP SWITCH POSITION
1 2 MODE
OFF OFF 2-10V
OFF ON 0-10V
ON OFF 10-2V
ON ON 10-0V
PROPORTIONAL/MODULATING: 4-20mA CONTROLLER OUTPUT WITH
500Ω SERIES RESISTOR
TO OTHER
ACTUATORS
500 OHMS,
1/2 W
MINIMUM
24 VAC
RED
BLACK
WHITE
1
PROPORTIONAL ACTUATOR
24 VAC
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
24 VDC SUPPLY ACCEPTABLE.
0 (2)-10 VDC
CONTROLLER
M33140A
1
2
3
+
+
DIP SWITCH POSITION
1 2 MODE
OFF OFF 2-10V
OFF ON 0-10V
ON OFF 10-2V
ON ON 10-0V
PROPORTIONAL/MODULATING: 0(2)...10 VDC OR 10...0(2) VDC CONTROLLER OUTPUT
2
RED
BLACK
WHITE
2
1