63-1301 B.B. 10-04 www.honeywell.com
/building/components/
VGF FLANGED GLOBE VALVES
TYPICAL SPECIFICATION
Automatic control valves shall have flanged fittings,
2-1/2 in. through 6 in. sizes, and shall be ANSI-rated
to withstand the pressures and temperatures
encountered.
Valves shall have metal-to-metal seats, stainless-
steel stems, and replaceable spring-loaded
reinforced carbon-filled teflon packing.
Valves shall have a maximum leakage rate of
0.05% Cv at the control port.
Valves shall have a 50:1 rangeability or better.
All two-way water valves shall be provided with
equal-percentage contoured throttling plugs. All
chilled water or steam valves shall be provided with
linear contoured throttling plugs.
Three-way valves shall be available in either mixing
or diverting configurations.
Water should be properly filtered, treated and
conditioned according to local conditions. The
installation of a strainer is strongly recommended.