Table of Contents Relay Programming ................................................ 25 Relay Voice Descriptors ......................................... 28 Relay Voice Descriptors and Custom Word Substitutes Vocabulary........................................ 29 Custom Word Substitutes for VIP Module Annunciation........................................................ 30 System Layout Worksheets.................................... 31 Relay Devices Worksheets.....................................
Recommended Programming Procedure The following is a step-by-step procedure recommended for programming your VISTA-50P/VISTA-50PUL system. 1. Set the keypads (and other peripheral devices) to the appropriate addresses. 2. Set factory defaults by pressing ✱97. This will automatically enable keypad addresses 00-03, so be sure at least one keypad is set to one of these addresses. 3. Program system-wide (global) data fields.
Program Field Index On the following pages, the programming fields have been arranged in numerical order. Use this index to cross-reference the fields on the programming form.
VISTA-50P/VISTA-50PUL Programming Form Some fields are programmed for each partition (shown as shaded fields). If you are programming a multiple-partition system, see the Partition-Specific Fields section for programming these fields. Standard default (*97) values are shown in brackets [ ]. | | | *00 INSTALLER CODE *25 BURG.TRIGGER FOR RESPONSE TYPE 8 Enter 4 digits, 0-9 [4140] *02 *05 [1] 1=enable; 0=disable RESPONSE TYPES FOR ZONES *26 INTELLIGENT TEST REPORTING Skip these fields.
*39 ENABLE OPEN/CLOSE REPORT FOR *58 SUPERVISORY AND RESTORE CODES FOR ZONES [0] 01-16. Enter 00-09; B-F (11-15). Default = [00 00 00 00 00] INSTALLER CODE 1=enable; 0=disable *40 OPEN/CLOSE REPORT FOR KEYSWITCH [0] *59 1=enable; 0=disable *41 NORMALLY CLOSED or EOLR (Zones 2-8) *62 [1] | | | Trbl Rst Byp Byp Rst ALARM REPORT CODES & ID DIGITS FOR ZONES 17-32. *63 SUPERVISORY AND RESTORE CODES FOR ZONES *42 DIAL TONE PAUSE 17-32. Enter 00-09; B-F (11-15).
*80 *81 SYSTEM NON-ALARM CODES Enter 00-09; B-F (11-15). Default = 00 for all reports *80 1st Digit 1*20 EXIT ERROR LOGIC ENABLE 0=No; 1=Bypass E/E and Interior zones faulted after exit delay. Must be "0" for UL installations.
1*40 1*41 NON-ALARM DIALER CODES Enter 00-09; B-F (11-15). Default = 00 for all reports 1*40 1st Digit 1*58 5800 RF BUTTON FORCE ARM Enter "1" to enable. If a zone is faulted after pressing button, keypad will beep once. Pressing the button again within 4 sec. bypasses the zone. Enter "0" to disable. Must be "0" for UL installations.
2*06 AUTO-ARM WARNING PERIOD | [15] 2*18 ENABLE GOTO FOR THIS PARTITION This is the time during which the user is warned to exit the premises prior to the auto-arming of the system (beeps every 15 seconds; "ALERT" displayed). Enter 01-15 minutes. 00=instant at end of arming delay.
Partition-Specific Fields (Duplicate this page for each partition in the installation.) To program these fields, 1. Press *91 to select a partition. 2. Enter a partition-specific field number (ex. *09). 3. Make the required entry. 4. Repeat steps 1-3 for each partition in the system.
3rd Page Programming Fields (press *94) 2*05 AUTO-ARM DELAY 2*18 ENABLE GOTO FOR THIS PARTITION | [15] 1=Allow log-on from other partitions; 0=disable Enter the time between the end of the arming window and the start of auto-arming warning period, in values of 1-14 times 4 minutes 00=instant; [15=no auto arm at all]. When this delay expires, the Auto-Arm Warning Period begins.
Programming With #93 Menu Mode NOTE: The following field should be preset before beginning: 2*00 Number of Partitions. In addition, receivers should be programmed via Device programming. After programming all system related programming fields in the usual way, press #93 while still in programming mode to display the first choice of the menu driven programming functions. Press 0 (NO) or 1 (YES) in response to the displayed menu selection. Pressing 0 will display the next choice in sequence.
Zone Programming If using 5800 Series transmitters, do not the install batteries until you are ready to enroll them. After enrolling the transmitter, the battery need not be removed. This is to prevent enrolling the wrong serial number. PROMPT EXPLANATION ZONE PROG? 1 = YES 0 = NO 0 SET TO CONFIRM? 1 = YES 0 = NO 0 ENTER ZONE NO. 00 = QUIT Press 1 to enter ZONE PROGRAMMING mode. The following screens appear. Press [✱] to display the next screen. Press # to display a previous screen.
PROMPT EXPLANATION 10 INPUT TYPE RF Xmitter Enter the input device type as follows: 00 = not used 01 = hardwired 03 = supervised RF transmitter (RF type) 04 = unsupervised RF transmitter (UR type) 05 = RF button-type transmitter (BR type) 06 = serial number polling loop device (SL type) 07 = DIP switch-type polling loop device 08 = right loop of DIP switch type device Right loops refer to the use of the right loop on a 4190WH Zone Expander Module and/or 4278 PIR, which allow hardwired devices to be monit
5800 Series Transmitters Loop Designations LOOP 3 LOOP 2 (REED) LOOP 1 (PRIMARY) LOOP 2 LOOP 2 (AUX.
PROMPT EXPLANATION ENTER ZONE NO. 00 = QUIT The system now returns to the “ENTER ZONE NO.” prompt for the next zone. When all zones have been programmed, enter “00” to quit. 11 After you have enrolled each wireless device, remove ONE of the serial number labels from that device and affix it in the appropriate column on the worksheets provided later in this Programming Guide; then enter the other information (zone number, zone type, etc.) relevant to that device.
PROMPT EXPLANATION Zn ZT P RC 10 03 1 10 Enter all zone information except for Loop number, or press “C” to copy the zone information on this screen from the last saved zone (including Loop). ZT = Zone Type P = Partition RC = Report Code In = Input Device Type L = Loop number to which the sensor is connected. NOTE: Pressing the [C] copies the zone information from the last saved zone, which includes the input type. Verify this information is correct for this zone.
Entering Wireless Keys If you pressed the D key previously to enter defaults for 5804 and/or 5804BD wireless keys, the following screens appear: PROMPT EXPLANATION FROM TEMPLATE 1–6 1 Enter template number (1–6). 1–3 = 5804 templates; 4–6 = 5804BD templates. See the defaults provided for each template in the chart that follows these procedures. Select from templates. Press [✱] to display template (template 1 shown selected). Note: If necessary, press [#] to back up and re-enter template number.
Wireless Key Default Templates 5804 Template 1 Template 2 Template 3 5804BD Loop 1 2 3 4 Loop 1 2 3 4 Loop 1 2 3 4 Function No Response Disarming Arm AWAY No Response Function No Response Disarming Arm AWAY Arm STAY Function 24-Hour Panic Disarming Arm AWAY Arm STAY Zone Type 23 22 21 23 Zone Type 23 22 21 20 Zone Type 07 22 21 20 Template 4 Template 5 Template 6 – 19 – Loop 1 2 3 4 Loop 1 2 3 4 Loop 1 2 3 4 Function No Response No Response Arm AWAY Disarming Function No Response Arm STAY Arm AWA
Alpha Descriptors Programming You can program a user-friendly English language description/location for all protection zones, relays, keypad panics, polling loop short, and RF receiver supervision troubles. Each description can be composed of a combination of words (up to 3) that are selected from a vocabulary of 244 words stored in memory, and any word can have an "s" or " ’s " added to it.
4. 5. 6. 7. Accept the word. To accept the word, press [6], which switches back to the alphabet list for the next word, or press [8] to store the complete descriptor and then exit. Select the next word. For selection of the next word (DOOR), repeat step 3a (word #057) or 3b, but selecting the word "DOOR.” To accept the word, press [6], which again switches back to alphabet list. Store the descriptor. When all desired words have been entered, press [8] to store the description in memory.
2. 3. 4. 5. 6. 7. Enter the custom word number (01-20) you want to create. For example, if you are creating the first word (or word string), enter 01; when creating the second word, enter 02, and so on. A cursor now appears at the beginning of the second line. Type the word using one of two methods as follows: a) Press [#], followed by the 2-digit entry for the first letter you would like to display (e.g., 65 for "A"). When the desired character appears, press [6] to select it.
Alpha Descriptor Vocabulary (For entering alpha descriptors. To select a word, press [#] followed by the word’s 3-digit number.) NOTE: This vocabulary is not to be used for relay voice descriptors. See the Relay Voice Descriptors section when programming relay voice descriptors.
Device Programming This menu is used to program keypads, receivers, and relay modules, etc. Device Address 00 is always set as an alpha keypad assigned to Partition 1 with no sounder suppression options, and these settings cannot be changed. From Data Field Programming mode, press #93 to display "ZONE PROG?" Press [0] repeatedly to display "DEVICE PROG?" PROMPT EXPLANATION DEVICE PROG? 1=YES 0=NO Press [1] to enter Device Programming.
Relay Programming The system supports up to 16 relays. Relays can be used to perform many different functions and actions. Each output must be programmed to begin one of three types of ACTIONS at a designated START event, and end that ACTION at a designated STOP event. The options used to start and stop these devices are described below, followed by the actual screen prompts and available entries.
Relay Devices Programming From Data Field Programming Mode, press #93 to display the "ZONE PROG?" prompt. Press [0] (NO) to each menu option until the "RELAY PGM?" prompt appears. Press [1] (YES). While in this mode, press [✱] to advance to next screen. Press [#] to back up to the previous screen. PROMPT EXPLANATION ENTER RELAY # (00=QUIT) 01 Enter the relay (output device) identification number 01-16. This is a reference number only, used for identification purposes.
PROMPT EXPLANATION 02 START: PARTN ANY PARTITION If the starting event will be limited to occurring on a specific partition, enter the partition number (1-8) in which the start event will occur. Enter 0 for any partition. Press [✱] to continue. 0 Do not use a zone programmed with an RF Button (Input Type BR) to STOP a relay. The system will not deactivate the relay. PROMPT EXPLANATION 02 STOP: ZN LIST If a zone list is being used to stop this relay action, enter the zone list number, 1-8.
If you are defining a zone list, continue to the next section. If not, enter 00 + [✱] at the next two prompts. You will then be asked "Quit Menu Mode?" Enter 1 for "Yes," 0 for "No." Then enter ✱99 to exit programming completely. Zone List Programming After all relays have been programmed, upon entering 00 at the "ENTER RELAY NO." prompt, you are asked to enter a zone list.
PROMPT EXPLANATION 01 ENTER DESC d1 From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3-digit index number for the first word of the relay descriptor phrase. Press [✱] to accept entry. 01 ENTER DESC d2 From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3-digit index number for the second word of the relay descriptor phrase. If second word is not desired, press [000]. Press [✱] to accept entry.
Custom Word Substitutes for VIP Module Annunciation A substitute word can be programmed for each of the 20 custom words used in your alpha zone descriptions. The VIP Module announces this substitute word in place of the custom word that is displayed on the alpha keypad. For example, an alarm display of "John’s Bedroom" could be announced as "Son’s Bedroom," as there is no annunciation for the custom word "John.
System Layout Worksheets Before programming any security system, you should first define the installation. To help you lay out a partitioned system, use the following worksheets. This will further simplify the programming process. PARTITIONS Partition # Partition 1 Descriptor (4-char max) Prim. Sub. # Sec. Sub.
PRINTER OPTIONS EVENT LOG TYPES Option 12- or 24-hour Time format Printer On-Line (yes/no) No Yes Alarm Trouble 1200 or 300 baud Printer Baud Rate Bypass Open/Close System DEVICES (keypads, 4204, rf receivers, vip module) Addr 00. 01. 02. 03. 04. 05. 06. 07. 08. 09. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30.
ACCESS CODES & USER DEFINITIONS FOR PARTITIONS 3 & 4 4-digit Security Code Access Group 0; 1-8 4-digit Security Code Access Group 0; 1-8 4-digit Security Code Access Group 0; 1-8 2-Digit User # Auth. Level Partition 3 Open/ Close RF Key Global Arm 2-Digit User # Auth. Level Partition 4 Open/ Close RF Key Global Arm RF Key Global Arm RF Key Global Arm ACCESS CODES & USER DEFINITIONS FOR PARTITIONS 5 & 6 2-Digit User # Auth.
— 34 — 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Zone No. Zone Type Part 1-8 Input Type Serial # / Loop Rpt. Code ZONE DEFINITION FOR ZONES 01-25 Zone Information (part numbers) & Alpha Descriptor (3 words max.
— 35 — 50 49 48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 31 30 29 28 27 26 Zone No. Zone Type Part 1-8 Input Type Serial # / Loop Rpt. Code ZONE DEFINITION FOR ZONES 26-50 Zone Information (part numbers) & Alpha Descriptor (3 words max.
— 36 — 75 74 73 72 71 70 69 68 67 66 65 64 63 62 61 60 59 58 57 56 55 54 53 52 51 Zone No. Zone Type Part 1-8 Input Type Serial # / Loop Rpt. Code ZONE DEFINITION FOR ZONES 51-75 Zone Information (part numbers) & Alpha Descriptor (3 words max.
— 37 — 86 85 84 83 82 81 80 79 78 77 76 Zone No. Zone Type Part 1-8 Input Type Serial # / Loop Rpt. Code ZONE DEFINITION FOR ZONES 76-86 Zone Information (part numbers) & Alpha Descriptor (3 words max.
ZONE DEFINITIONS FOR KEYPAD PANIC ZONES 95, 96, & 99 Enter yes/no for each partition-field *22 Zone No. Zone Type 1 2 3 4 5 6 7 8 Report Code Zone Information (part numbers) & Alpha Descriptor (3 words max.) 95 96 99 ZONE DEFINITIONS FOR SYSTEM ZONES; 88; 89, 90, 91, 97 & 98 Zone No. Zone Type Zone Information (part numbers) & Alpha Descriptor (3 words max.
Relay Devices Worksheets Applicable only if relays (4204), or X-10 devices are used. Relays are programmed in the #93 Menu Mode in the Relay Programming Section. Fill in the required data on the worksheet below and follow the procedure in the Installation and Setup Guide as you enter the data during the displays and prompts that appear in sequence. Notes: 1. For 4204 the Device Programming section must be programmed for the device address. Set the DIP switches on the device for that address. 2.
ZT = ZONE TYPE/SYSTEM OPERATION Choices for Start/Stop Zone Types and System Operations: 00 = No Response (Not Used) 23 = No Alarm Response 43 = Communication failure 01 = Entry/Exit #1 31 = End of Exit Time 44 = RF Low Battery 02 = Entry/exit #2 32 = Start of Entry Time 45 = Polling Loop Failure 03 = Perimeter 33 = Any Burglary Alarm 51 = RF Receiver Failure 04 = Interior Follower 34 = Code + [#] + 71 Key Entry 52 = Kissoff 05 = Trouble Day/Alarm Night 35 = Code + [#] + 72 Key Entry 54 = Fire Zone Reset
Zone List 7: Started or stopped by zone numbers (enter 000 to end entries). Zone List 8: Started or stopped by zone numbers (enter 000 to end entries). Scheduling Menu Prompts To program schedules, enter Scheduling program mode by pressing [User Code] + # + 80 to display the first choice of the menu driven programming functions. NOTE: Only users with an Installer or Master level user code may enter the #80 mode. Press 0 (NO) or 1 (YES) in response to the displayed menu selection.
Scheduling Worksheets Time Windows Definitions Worksheet. The system provides 20 time windows that are defined with start and stop times. They are programmed in the #80 Menu Mode. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.
Holiday Schedule Worksheet: The system provides up to 16 holidays that can be assigned for the system. Each holiday can be assigned to any combination of partitions. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.
Below is a list of the "Action" codes (desired actions) used when programming time-driven events. Note that these codes are independent of the "relay codes" programmed during the #93 Menu Mode–Relay Programming mode. If using Time Driven Events, the following menu items must first be programmed using #93 Menu Mode - Relay Programming: ECP Address Relay No. House Code Unit Code Enter Relay No.
Temporary Schedule #81 Menu Mode. The system provides a Temporary Schedule for each partition. Enter the temporary scheduling mode by pressing [Installer Code] + [#] + [81]. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.
Partition/Windows 7 Mon Tue Wed Disarm Window Start Time HH:MM Stop Time HH:MM Arm Window 8 Start Time HH:MM Stop Time HH:MM Disarm Window Start Time HH:MM Stop Time HH:MM Arm Window Start Time HH:MM Stop Time HH:MM — 46 — Thu Fri Sat Sun
RED (+) CHARGING VOLTAGE 13.7VDC See Installation Instructions for required capacity Connect to 24hr. 120VAC, Replace 60 Hz Outlet every 3 years BLK (–) — 47 — 3 SIREN – BELL + 2 5 Blk – 7 Grn Yel 9 8 – For Household Fire Installations, supervise alarm sounder output (Note 5) and limit combined alarm sounder, aux power and polling loop current to 750mA. SMOKE 2k EOLR (note 1,2) N.O. – 11 ZONE 1 N.C. + 10 2k EOLR (note 1) N.O. N.C. – 16 N.C. 2k EOLR (note 1) N.O. N.O. N.