TrueFRESH Installation Manual

TrueFRESH™ ERV/HRV Ventilation Systems 69-2480EF—17 23
Installation Steps (continued)
Optional Matrix hood (50063805-009) installation for fresh air and
exhaust air
7b
See Matrix hood literature for step-by-step
instructions.
NOTE: Only for applications up to 115 CFM maximum speed. Higher airflow rates are limited by higher
static pressures and the potential of cross-contamination between the supply and exhaust air
streams. The Matrix hood design is suitable for smaller spaces commonly found in town homes and
condominiums which require less airflow rates.
NOTE: A 6 in. to 5 in. reducer is required if you are installing the matrix hood (50063805-009) with the
VNT5070.