Instructions / Assembly

VR8245 AND VR8345 UNIVERSAL ELECTRONIC IGNITION GAS CONTROLS
69-2013—02 10
Standard-Opening Pressure Regulator
1. The gas control outlet pressure should match the
manifold pressure listed on the appliance name-
plate.
2. With the main burner operating, check the gas con-
trol flow rate by using the meter clocking method or
check the gas pressure using a manometer con-
nected to the gas control outlet pressure tap. See
Fig. 3.
3. If necessary, adjust the pressure regulator to match
the appliance rating. Refer to Table 6 for the factory
set nominal outlet pressures and adjustment setting
ranges.
a. Remove the pressure regulator adjustment cap
screw.
b. Using a screwdriver, turn the inner adjustment
screw clockwise to increase or counter-
clockwise to decrease the main burner gas
pressure.
c. Always replace the cap screw and tighten firmly
to safeguard proper operation.
4. If the desired outlet gas pressure or gas flow rate
cannot be achieved by adjusting the gas control,
check the gas control inlet pressure by using a
manometer at the inlet pressure tap. If the inlet
pressure is in the normal range (refer to Table 6 and
7), replace the gas control. Otherwise, take the nec-
essary steps to provide proper gas pressure to the
gas control.
Standard and Slow-Opening (H and M)
Models
1. Carefully check the main burner lightoff. Make sure
that the main burner lights smoothly and that all
ports remain lit.
2. Check the full rate manifold pressure listed on the
appliance nameplate. Gas control full rate outlet
pressure should match this rating.
3. With main burner operating, check the control flow
rate using the meter clocking method or check pres-
sure using a manometer connected to the outlet
pressure tap on the control. See Fig. 3.
4. If necessary, adjust the pressure regulator to match
the appliance rating. See Table 6 and 7 for factory-
set nominal outlet pressure and adjustment range.
a. Remove the pressure regulator adjustment cap
screw.
b. Using a screwdriver, turn the inner adjustment
screw (Fig. 3) clockwise to increase or
counterclockwise to decrease the gas pres-
sure to the burner.
c. Always replace the cap screw and tighten firmly
to prevent gas leakage.
5. If the desired outlet pressure or flow rate cannot be
achieved by adjusting the gas control, check the
gas control inlet pressure using a manometer at the
inlet pressure tap of the gas control. If the inlet pres-
sure is in the nominal range (see Table 6 and 7),
replace the gas control. Otherwise, take the neces-
sary steps to provide proper gas pressure to the
control.
Two-Stage (Q) Models
Two-stage models require that you check and adjust both
high and low pressure regulator settings. Two-stage
appliance operating sequences vary. Consult the
appliance manufacturer instructions for the specific
operating sequence and regulator adjustment procedure
for the appliance in which the control is installed.
1. Set appliance to operate on high.
2. Carefully check the main burner lightoff. Make sure
that the main burner lights smoothly and that all
ports remain lit.
3. Check the full rate (high) manifold pressure listed
on the appliance nameplate for high pressure. The
gas control full rate outlet pressure should match
this rating.
4. With main burner operating, check the gas control
flow rate using the meter clocking method or check
pressure using a manometer connected to the out-
let pressure tap on the gas control. See Fig. 3.
5. If necessary, adjust the high pressure regulator to
match the appliance rating. See Table 6 and 7 for
factory-set nominal outlet pressure and adjustment
range.
a. Remove the pressure regulator adjustment cap
(Fig. 3).
b. Using a screwdriver, turn the inner adjustment
screw for HI pressure clockwise to increase
or counterclockwise to decrease the gas
pressure to the burner.
6. After high pressure has been checked, check low
pressure regulation. Two-stage appliance operating
sequences vary. Consult the appliance manufactur-
ers instructions for the specific operating sequence
and regulator adjustment procedure for the appli-
ance in which the control is installed and for instruc-
tions on how to prevent the control from moving to
high stage while checking the low pressure regula-
tor setting.
7. Check the low rate manifold pressure listed on the
appliance nameplate. Gas control low rate outlet
pressure should match this rating.
8. With main burner operating, check the gas control
flow rate as before (using the meter clocking
method or check pressure using a manometer con-
nected to the outlet pressure tap on the control).
9. If necessary, adjust the low pressure regulator to
match the appliance rating. See Table 6 and 7 for
factory-set nominal outlet pressure and adjustment
range.
a. Remove the pressure regulator adjustment cap
(Fig. 3). Using a screwdriver, turn the inner
adjustment screw for LO pressure clockwise
to increase or counterclockwise to
decrease the gas pressure to the burner.
10. Once high and low pressure have been checked
and adjusted, replace pressure regulator adjust-
ment cap. If the desired outlet pressure or flow rate
cannot be achieved by adjusting the gas control,
check the control inlet pressure using a manometer
at the inlet pressure tap of the control. If the inlet
pressure is in the nominal range (see Table 6 and
7), replace the gas control. Otherwise, take the nec-
essary steps to provide proper gas pressure to the
control.