Instructions / Assembly

VR8245 AND VR8345 UNIVERSAL ELECTRONIC IGNITION GAS CONTROLS
69-2013—02 6
Fig. 8. Remove pilot gas seal (plug) and install pilot
gas tube for intermittent pilot application on VR8345.
WIRING
CAUTION
Disconnect power supply before making
wiring connections to prevent electrical shock
or equipment damage.
Follow the wiring instructions furnished by the appliance
manufacturer, if available, or use the following general
instructions. Where these instructions differ from the
appliance manufacturer, follow the appliance
manufacturer instructions.
All wiring, including insulated quick connect terminals,
must comply with applicable electrical codes and
ordinances.
1. Check the power supply rating on the gas control
and make sure it matches the available supply.
Install thermostat and other controls as required.
2. When the gas control is installed on a hot surface or
direct spark ignition system, attach the wire adapter
provided to the wiring terminals. See Fig. 9 for the
wire terminal location.
3. Connect control circuit to gas control terminals. See
Fig. 3 and 10, 11, 12, or 13.
4. Adjust the thermostat heat anticipator to 0.7, the
rating stamped on the valve operator.
Fig. 9. Install wire adapter for hot surface or direct
spark ignition systems. Pilot plug must be in the valve
pilot opening.