Product Overview

2
W7100A-E
Specifications
MODELS: W7100 Discharge Air Controller—see Table 1.
TABLE 1—W7100 DISCHARGE AIR CONTROLLER MODELS.
Ordering Information
When purchasing replacement and modernization products from your Honeywell distributor, refer to the TRADELINE
®
Catalog
for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Satisfaction
Honeywell Inc., 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Honeywell Limitée, 740 Ellesmere Road, Scarborough, Ontario M1P 2V9 International
Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany,
Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
SPECIFICATIONS • ORDERING INFORMATION
Modulating
Heat
Modulating
Cooling Heating Cooling
Temperature Range
Model Economizer
Output Output Stages
a
Stages
a
°F °C
W7100A Yes No No None 6 40° to 90° 4° to 32°
W7100B Yes No No 6 None 40° to 140° 4° to 60°
W7100C Yes No No 2 4 40° to 90° 4° to 32°
W7100D Yes Yes
b
Yes
b
None
c
None
c
40° to 140° 4° to 60°
W7100E Yes Yes No 1 4 40° to 90° 4° to 32°
a
Number of W7100 stages can be increased by six stages—four cool and two heat, or two cool and four heat, using W7101
Satellite Sequencer (except W7100E).
b
W7100D has single selectable modulating output—either heat or cool.
c
W7100D heating and cooling stages are not designed for use with the W7101 Satellite Sequencer.
ELECTRICAL RATINGS:
Input Voltage and Frequency (terminals TR-TR): 20 to
30 Vac at 60 Hz; 20 to 26.4 Vac at 50 Hz.
Power Consumption: 12 VA at 24 Vac, 50 to 60 Hz.
Contacts Voltage (V)
Inrush
(VA)
Running
(VA)
N.O. 24 240 60
N.C. 24 75 30
N.O. 120/240 750 75
N.C. 120/240 240 40
SWITCHING (on/off stages): Spdt relays.
WIRING TERMINALS: 1/4 in. [6 mm] quick-connect
type.
INPUT SIGNAL (DA sensor): Positive temperature coeffi-
cient of 4.8 ohms/degree F [8.6 ohms/degree C], resis-
tance of 3484 ohms at 77° F [25° C].
CONTROLLED STAGES: Resistor value (across termi-
nals 7 and 8) to determine number of on-off stages
controlled by W7100. Varies from 100 ohms for one
stage to 1000 ohms for 10 stages with W7101 (see
Table 2).
AMBIENT TEMPERATURE RANGE: -40° F to +150° F
[-40°C to +60° C].
MOUNTING: Four mounting holes in base accept No. 8
screws (screws not provided).
DIMENSIONS: See Fig. 1.
APPROVALS:
Underwriters Laboratories Inc. Component Recognized:
Guide no. SDFY2, file no. SA481.
Canadian Standards Association Certified: Guide no.
400-E-0, file no. 46034.
ADDITIONAL SYSTEM COMPONENTS:
C7100A1015 Discharge Air Averaging Sensor (re-
quired): Senses average DA temperature; provides
input to W7100 sensor terminals T and T1.
Transformer (required): Provides 24 Vac power for all
components of the W7100 Control System (size trans-
former to match system load).