Product Overview

22
W7100A-E
Fig. 19Outdoor reset.
Fig. 20Series/parallel resistance wiring for
W7100 reset.
MECHANICAL SETPOINT
FULL RESET
NO
RESET
ADJUSTABLE RESET
5° - 20° FOR COOL
20° - 80° FOR HEAT
T-LOW T-HIGH
M3902
OUTDOOR RESET
Using the applicable table (cooling or heating), select
the point at which no reset to the W7100 setpoint will occur
W7100
TERMINALS
M3903
C7031G1016
RESISTOR
PARALLEL
RESISTOR
SERIES
(RS)
(RP)
6
7
(T-HIGH) and the point at which you desire the W7100 to
be fully reset (T-LOW). At the intersection of the two
points is the value of the resistor to be placed in series (R
s
)
and the value of the resistor to be placed in parallel (R
P
).
Indicated resistor values are standard resistors and can be
purchased locally.
TABLE 3SERIES/PARALLEL RESISTORS FOR COOLING.
T-HIGH
T-LOW (FULL RESET)
(NO RESET)
75 70 65 60 55 50
100 RP 14.7K 8.2K 5.6K 4.4K 3.6K 3.1K
RS 200 310 415 490 560 620
95 RP 14.7K 8.2K 5.6K 4.4K 3.6K
RS 190 300 410 485 560
90 RP 14.7K 8.2K 5.6K 4.4K
RS 180 295 400 480
85 RP 15.0K 8.4K 5.6K
RS 170 280 395
80 RP 15.0K 8.4K
RS 160 275
75 RP 15.0K
RS 150
TABLE 4SERIES/PARALLEL RESISTORS FOR HEATING.
T-HIGH
T-LOW (FULL RESET)
(NO RESET)
30 25 20 15 10 0
60 RP 8.6K 5.9K 4.6K 3.8K 3.3K 2.6K
RS 240 350 430 500 560 660
55 RP 17.5K 8.6K 5.9K 4.6K 3.8K 2.9K
RS 90 230 340 420 500 610
50 RP 17.5K 8.8K 6.0K 4.6K 3.3K
RS 80 220 330 420 550
45 RP 17.5K 8.8K 6.0K 3.9K
RS 70 210 320 480
40 RP 17.5K 8.8K 4.7K
RS 60 200 400
35 RP 8.8K
RS 190
OPERATION