Safety Guide

XNX Universal Transmitter
Proof Testing Procedure 13
Testing
Figure 17. Conrmation
Selecting
will simulate the selected alarm. If the
is
selected, the simulation is aborted.
4. To simulate a Warning or Fault from the XNX, select the
appropriate icon from the menu.
Figure 18. Warning and Fault Simulation Screens
5. As in an alarm simulation, a confirmation screen will appear.
Selecting
will simulate a warning or fault from the XNX. If
is selected, the simulation is aborted.
Figure 19. Fault Simulation Conrmation
6. Use Alarm/Fault Reset to reset alarms, faults or warnings
generated by the simulation.
Figure 20. Alarm/Fault Reset Screen
As in an alarm simulation, a confirmation screen will appear.
Figure 21. Alarm/Fault Reset Screen
Selecting
will reset all alarms, faults or warnings generated
by the simulation. If
is selected, the simulation continues.
CAUTION
The alarms and faults generated by the simulation will not be
cleared from the XNX until alarms/faults are reset. Failure to reset
the alarms/faults upon exiting the simulation keeps the relays and
LEDs in alarm/fault mode.
6.4.2 Gas Verification
To verify the mA output of Zero Gas and Calibration, refer to 6.1. 2 and
6.1. 3.
A different bottle of calibration gas and/or zero gas should be used
to verify the results.