Section 1 - Introduction
15
states. Two alarm levels can be set, allowing, for example, a level
1 alarm for the immediate area when a certain gas concentration
is detected and a plant-wide level 2 alarm when a greater gas
concentration is detected.
The maximum refresh rate of the relays is 2 seconds. See Set
Alarm Values for more information.
1.3.3 Modbus
The optional Modbus interface allows the XNX to connect to
a bus of devices and transmit data to PLCs or controllers.
(For more information, see the Modbus
Protocol Manual).
Connections to the XNX are made through a pluggable terminal
block on the Modbus interface circuit board. Modbus RTU
protocol uses ASCII/Hex protocols for communication.
Note: POD options are either relay, Modbus, or Foundation Fieldbus.
1.3.4 Foundation Fieldbus
Foundation Fieldbus is a digital communication system which
supports several types of messages. Unlike many traditional
systems which require a set of wires for each device, multiple
Foundation Fieldbus devices can be connected with a
single set of wires. Foundation Fieldbus overcomes some
of the disadvantages of proprietary networks by providing a
standardized network for connecting systems and devices.
1.3.5 XNX Accessories
Pipe Mount Kit
The Pipe Mount kit (1226A0358) allows the XNX to be mounted
to pipe from 2”-6” (50-150mm) in diameter. The kit includes the
pipe mount bracket, two carriage bolts, nuts, and lock washers.
Figure 8. Pipe-mounted XNX Transmitters
Calibration Gas Flow Adapter
The calibration gas ow adapter is used to apply calibration
test gas to the sensor. It attaches to the bottom of the sensor
and can be tted without removing the weatherproof cover. See
Section 3 - Calibration for further details on gas calibration.
Sensor Flow Adapter P/N
XNX EC S3KCAL
MPD 1226A0411
Sensepoint 02000-A-1645
705 00780-A-0035