Submittal Sheet

SPECIFICATION DATA
31-00124-01
LCBS Connect
Controller and Wall Module
GENERAL
The LCBS Connect controller and wall module
combination have been designed to control Constant
Volume Air Handling Unit, Heat Pump application, and
their configurations. With the embedded control logic and
integral temperature, humidity sensors, they control the
space temperature in a given zone by regulating the
heating and cooling equipment that delivers conditioned
air to that space. In addition to standard heating and
cooling control, they provide advanced control options
making them a state-of-the-art commercial building
control solution. The control can be done as a stand-alone
operation, however, when implemented with network
communication capabilities, optimal functional benefits
are achieved. These additional features are available
through the connection to an LCBS Connect gateway
which will enable access to the Honeywell cloud.
SPECIFICATIONS
Electrical
Rated Voltage: 20-30 Vac; 50/60 Hz
Power Consumption:
100 VA for controller and all connected loads
Controller only Load: 5 VA maximum
External Sensors Power Output: 20 Vdc ±10% @ 75 mA
maximum
Environmental
Controller Operating & Storage Temperature Ambient
Rating:
Minimum: -40° F (-40° C); Maximum: 150° F (65.5° C)
Relative Humidity: 5% to 95% non-condensing
Wall Module Operating Temperature: 32°F to 122°F
(0°C to 50°C)
Wall Module Storage Temperature: -4°F to 150°F (20°C
to 65°C)
Relative Humidity: 5% to 95%, Non-condensing
Controller Real Time Clock
Operating Range: 24 hour, 365 day, multi-year calendar
including day of week and configuration for automatic
daylight savings time adjustment to occur at 2:00 a.m.
local time on configured start and stop dates
Power Failure Backup: 24 hours at 32 to 100° F (0 to 38°
C), 22 hours at 100 to 122° F (38 to 50° C)
Accuracy: ±1 minute per month at 77° F (25° C)
Wall Module Accuracy
Temperature: ±0.36° F at 77° F (±0.2° C at 25° C)
Humidity: ±3% RH from 20–80%RH
Approval Bodies
UL/cUL (E87741) listed under UL916 (Standard for Open
Energy Management Equipment) with plenum rating.
CSA (LR95329-3) listed.
Meets FCC Part 15, Subpart B, Class B (radiated
emissions) requirements.