Submittal

Prestige
®
IAQ and Prestige
®
2.0
Thermostats
Job Name
Engineer
Mechanical Contractor
Contractor’s P.O. No.
Representative
Notes
Model(s) Qty. Qty.
THX9421R5021WW
THX9421R5021BB
THX9421R5021SG
Approval
Service
Tag No.
SUBMITTAL SHEET
APPLICATION
The Prestige IAQ and Prestige 2.0 are 7-Day programmable
thermostats with auto changeover that are designed for single stage
and multistage control of conventional and heat pump equipment
such as rooftop units and split systems in residential and commercial
applications. The thermostats control up to 3 heat / 4 cool conventional
systems and up to 4 heat / 2 cool heat pump systems. The thermostat
controls humidication, dehumidication, ventilation, an economizer
and a lighting panel. Prestige IAQ has universal sensor inputs that
are used with remote indoor air temperature sensor(s), an outdoor air
temperature sensor, a discharge air temperature sensor, a return air
temperature sensor, an occupancy sensor for remote setback and dry
contact devices for displaying alerts.
The thermostats are equipped with a 16:9 touchscreen TFT color
display (WQVGA - 480 x 272 pixels).
Provides a USB port to upload Dealer Information, Custom
Reminders, Custom Event Schedules, Holiday Schedule and
Software Updates* and to download Data Logs.
Provides remote access to the thermostat when used with the
RedLINK internet gateway.
Provides control using optional remote temperature and humidity
sensors.
Prestige IAQ integrates with the Niagara-AX framework.
* Software Updates only applies to Prestige IAQ.
SPECIFICATIONS
Terminal Designations:
Equipment Interface Module: R, RC, RH, C, W-O/B, W2-AUX 1, W3-
AUX 2, Y, Y2, G, A-L/A, U1 U1, U2 U2, U3 U3, S1 S1, S2 S2, S3
S3, S4 S4, A, B, C, D
THX9421 Thermostat: R, C
THX9321 Thermostat: R, RC, C, W-O/B, W2-AUX/E, Y, Y2, G, A-L/A, K,
U1 U1, U2 U2
Electrical Ratings (for THX9321 and Equipment Interface
Module):
Terminal Voltage
(50/60 Hz)
Max. Current
Rating
W - O/B 18 to 30 VAC
and 750 mVDC
1.00A
Y (cooling) 18 to 30 VAC 1.00A
G (fan) 18 to 30 VAC 0.50A
W2 - Aux 1 (heating) 18 to 30 VAC 0.60A
W3 - Aux 2 (heating) 18 to 30 VAC 0.60A
Y2 (cooling) 18 to 30 VAC 0.60A
A-L/A (Output) 18 to 30 VAC 1.00A
(U1, U1), (U2, U2), (U3, U3) 18 to 30 VAC 0.50A
Power Consumption of THX9421/THX9321 Thermostat:
Full brightness = 3.0 VA
1/2 brightness = 2.1 VA
Backlight off = 1.9 VA
Power Consumption of Equipment Interface Module: 2.0 VA
RedLINK Communication:
Frequency: 900 Mhz frequency range
Re-Sync Time: RedLINK devices re-establish communication
within 6 minutes after AC power resumes.
Temperature Setting Range:
Heating: 40 to 90 °F (4.5 to 32 °C)
Cooling: 50 to 99 °F (10 to 37 °C)
Temperature Sensor Accuracy:
± 1.5 °F at 70 °F (0.75 °C at 21.0 °C)
Humidication Setting Range: 10% to 60% RH
Dehumidication Setting Range: 40% to 80% RH
Humidity Display Range: 0% to 99%
Humidity Sensor Accuracy:
± 5% RH from 30% to 50% RH at 75 °F (24 °C)
Cool Indication:
Displays “Cool On” when the thermostat turns the cooling on.
33-00017-01
THX9421R5021WG
THX9321R5030
THM5421R1021

Summary of content (2 pages)