THX9321 & THX9421 Product Data

Table Of Contents
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
125 68-0311—02
2. Select the terminals wired to the Remote Setback Dry
Contact device (occupancy sensor) and press Next.
Fig. 301.
3. Select Normally Open when Occupied or Normally
Closed when Occupied based on the type of dry contact
device installed.
NOTE: Normally Open when Occupied: The Dry Con-
tact device is open when the room is occupied
and will close when the room is unoccupied.
Normally Closed when Occupied: The Dry Con-
tact device is closed when the room is occupied
and will open when the room is unoccupied.
Fig. 302.
4. Select a Remote Setback Time Delay. The Remote Set-
back Time Delay forces the thermostat to wait before it
switches from occupied settings to the standby settings.
When set to 0 minutes, the thermostat will switch from
occupied settings to the standby settings immediately
when the room is unoccupied.
Fig. 303.
5. Select the Standby settings that you would like to main-
tain when the occupancy sensor detects the room is
unoccupied.
Fig. 304.