THX9321 & THX9421 Product Data
Table Of Contents
- Application
- Features
- Contents
- Specifications
- System Installation
- Installation Options
- Guidelines for Installing RedLINK Devices
- Installing Equipment Interface Module (if used)
- Wiring 24 Vac Common
- Selecting Discharge and Return Air Temperature Sensor Mounting Locations
- Selecting Return Air Temperature Sensor Mounting Location
- Installing Discharge and Return Air Temperature Sensors
- Selecting Thermostat Location
- Installing Wallplate
- Power Optional REDLINK™ Accessories
- Performing Initial Setup
- Linking Thermostat to Equipment Interface Module (if used)
- Linking RedLINK™ Accessories
- Completing Initial Setup
- Adding RedLINK Accessories to the Thermostat
- Locating the Connect Buttons on RedLINK Accessories
- Finding Your Password (Date Code) to Access Installer Options
- Installer Options
- Making Changes to Installer Setup
- Installer Tests
- Operation
- Setting the time/date
- Setting the fan
- Setting system mode
- Preset Energy-Saving Schedules
- Adjusting program schedules
- Overriding schedules: residential use
- Overriding schedules: commercial use
- Viewing equipment status
- Setting vacation hold: residential use
- Setting holiday/event schedules: commercial use
- Setting custom events: commercial use
- Setting holiday schedule: commercial use
- Setting holiday override: commercial use
- Initiating occupancy mode: commercial use
- Remote setback: commercial use
- Adjusting humidification settings
- Adjusting dehumidification settings: residential use
- Adjusting dehumidification settings: commercial use
- Adjusting ventilation settings
- Customizing screen color
- Setting preferences
- Cleaning the thermostat screen
- Adjusting security settings
- Viewing dealer information
- Advanced Features
- Installer options
- Using the temperature display
- Using the humidity display
- Universal Outputs (U1, U2, U3)
- Universal Inputs (S1, S2, S3, S4)
- Alerts and Diagnostics
- Heat Pump and Backup Heat Operation
- Indoor Air Quality (IAQ) Control
- IAQ Reminders
- Customizable Reminders
- USB Port
- Commercial Features
- Overriding schedules: commercial use
- Setting holiday/event schedules: commercial use
- Setting custom events: commercial use
- Setting holiday schedule: commercial use
- Setting holiday override: commercial use
- Initiating occupancy mode: commercial use
- Ramp Rates
- Custom Names
- Remote Setback
- Economizer and Time of Day (TOD) Operation
- Pre-Occupancy Purge
- Battery Replacement
- Optional Accessories
- Portable Comfort Control
- Remote Indoor Sensors
- Backup Control
- Replacing a Thermostat
- Replacing an Equipment Interface Module
- Wiring
- EIM Wiring Diagrams
- THX9321 Thermostat Wiring Diagrams
- THX9321 Thermostat Wiring Diagrams Using Universal Relays to Control Heating or Cooling
- Wiring IAQ Equipment or a Heat/Cool Stage to the Universal Terminals
- Economizer Module Wiring Diagrams
- Wiring C7089U1006 Outdoor Sensor
- Wiring guide — Wired Indoor Sensors
- Zoning
- Troubleshooting
- Regulatory Information
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—02 38
3150 Heat Cycles Per
Hour - Stage 1
Note: Depending
on the application,
the text displayed
on the screen may
show the specific
heating equipment
type. “Stage 1" is
not displayed if
there is only 1
stage.
1 to 12 CPH
Default varies
based on
heating
equipment type
selected
Both No ISU 3010 Temperature Control Options
must be set to Advanced to view or adjust
cycle rate.
This ISU is only displayed when ISU 2070
Heat Stages is set to 1 stage.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour
period measured at a 50% load. For
example, when set to 3 CPH, at a 50% load,
the most the system will cycle is 3 times
per hour (10 minutes on, 10 minutes off).
The system cycles less often when load
conditions are less than or greater than a
50% load. The thermostat automatically
defaults to the recommended cycle rate
based on the heating equipment type that is
used. You can change the cycle rate as
needed. Defaults for commonly used
systems are shown below.
Standard Efficiency Gas Forced Air = 5 CPH
High Efficiency Gas Forced Air = 3 CPH
Oil Forced Air = 5 CPH
Electric Forced Air = 9 CPH
Hot Water Fan Coil = 3 CPH
Hot Water Radiant Heat = 3 CPH
Geothermal Radiant Heat = 3 CPH
Steam = 1 CPH
Gravity = 1 CPH
3150 Heat Cycles Per
Hour - Stage 2
Note: Depending
on the application,
the text displayed
on the screen may
show the specific
heating equipment
type.
1 to 12 CPH
Default varies
based on
heating
equipment type
selected
Both No ISU 3010 Temperature Control Options
must be set to Advanced to view or adjust
cycle rate.
This ISU is only displayed when ISU 2070
Heat Stages is set to 2 stages.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour
period measured at a 50% load. For
example, when set to 3 CPH, at a 50% load,
the most the system will cycle is 3 times
per hour (10 minutes on, 10 minutes off).
The system cycles less often when load
conditions are less than or greater than a
50% load. The thermostat automatically
defaults to the recommended cycle rate
based on the heating equipment type that is
used. You can change the cycle rate as
needed. Defaults for commonly used
systems are shown below.
Standard Efficiency Gas Forced Air = 5 CPH
High Efficiency Gas Forced Air = 3 CPH
Oil Forced Air = 5 CPH
Electric Forced Air = 9 CPH
Hot Water Fan Coil = 3 CPH
Hot Water Radiant Heat = 3 CPH
Geothermal Radiant Heat = 3 CPH
Steam = 1 CPH
Gravity = 1 CPH
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes