THX9321 & THX9421 Product Data

Table Of Contents
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
47 68-0311—02
4120 Residential:
Entry / Exit Remote
- Home Heat
Setpoint
Commercial:
Entry / Exit Remote
- Occupied Heat
Setpoint
None
40° F to 90° F
Note: setpoint is limited based on
setting at ISU 4100.
70° F Both No The thermostat maintains this Heat setting
when the user presses Home / Occupied at
the Entry / Exit Remote. Select None to
delete this temperature setting. The
thermostat only responds to the Entry / Exit
Remote if a temperature is pre-set at this
screen. See “Wireless Entry/Exit Remote”
beginning on page 128.
4130 Residential:
Entry / Exit Remote
- Away Cool
Setpoint
Commercial:
Entry / Exit Remote
- Unoccupied Cool
Setpoint
None
50° F to 99° F
Note: setpoint is limited based on
setting at ISU 4100.
78° F Both No The thermostat maintains this Cool setting
when the user presses Away / Unoccupied
at the Entry / Exit Remote. Select None to
delete this temperature setting. The
thermostat only responds to the Entry / Exit
Remote if a temperature is pre-set at this
screen. See “Wireless Entry/Exit Remote”
beginning on page 128.
4130 Residential:
Entry / Exit Remote
- Away Heat
Setpoint
Commercial:
Entry / Exit Remote
- Unoccupied Heat
Setpoint
None
40° F to 90° F
Note: setpoint is limited based on
setting at ISU 4100.
65° F Both No The thermostat maintains this Heat setting
when the user presses Away / Unoccupied
at the Entry / Exit Remote. Select None to
delete this temperature setting. The
thermostat only responds to the Entry / Exit
Remote if a temperature is pre-set at this
screen. See “Wireless Entry/Exit Remote”
beginning on page 128.
4140 Residential:
Entry / Exit Remote
- Vacation Cool
Setpoint
Commercial:
Entry / Exit Remote
- Holiday Cool
Setpoint
None
50° F to 99° F
Note: setpoint is limited based on
setting at ISU 4100.
82° F Both No The thermostat maintains this Cool setting
when the user presses Vacation / Holiday at
the Entry / Exit Remote. Select None to
delete this temperature setting. The
thermostat only responds to the Entry / Exit
Remote if a temperature is pre-set at this
screen. See “Wireless Entry/Exit Remote”
beginning on page 128.
4140 Residential:
Entry / Exit Remote
- Vacation Heat
Setpoint
Commercial:
Entry / Exit Remote
- Holiday Heat
Setpoint
None
40° F to 90° F
Note: setpoint is limited based on
setting at ISU 4100.
60° F Both No The thermostat maintains this Heat setting
when the user presses Vacation / Holiday at
the Entry / Exit Remote. Select None to
delete this temperature setting. The
thermostat only responds to the Entry / Exit
Remote if a temperature is pre-set at this
screen. See “Wireless Entry/Exit Remote”
beginning on page 128.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes