THX9321 & THX9421 Product Data

Table Of Contents
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—02 54
7110 Air Filter 1
Replacement
Reminder
Note: “1” is not
displayed if there is
only 1 filter.
Off
Run Time:
10, 20, 30, 45, 60, 90, 120, 150
days
Calendar:
30, 45, 60, 75 days
3, 4, 5, 6, 9, 12, 15 months
Off Both No
7110 Air Filter 2
Replacement
Reminder
Off
Run Time:
10, 20, 30, 45, 60, 90, 120, 150
days
Calendar:
30, 45, 60, 75 days
3, 4, 5, 6, 9, 12, 15 months
Off Both No
7120 Electronic Air
Cleaner Cell
Cleaning Reminder
Off
Calendar Months:
6, 7, 8, 9, 10, 11, 12 months
Off Both No
7120 Electronic Air
Cleaner Pre-Filter
Cleaning Reminder
Off
Calendar Months:
3, 4, 5, 6 months
Off Both No
7120 Electronic Air
Cleaner Post-Filter
Replacement
Reminder
Off
Calendar Months:
6, 7, 8, 9, 10, 11, 12 months
Off Both No
8000 Humidifier Type
None
Steam
Bypass or Fan Powered
None Both No
8010 Which Sensor will
be used for
Humidification
Control?
Thermostat (Internal)
Sensor Name (Remote)
Sensor Name (Remote)
Sensor Name (Remote)
Sensor Name (Remote)
Sensor Name (Remote)
Sensor Name (Remote)
(Up to 6 Remote Sensors)
Thermostat
(Internal)
Both No Select a sensor to control humidification
(thermostat or an optional remote sensor).
If multiple sensors are installed, you can
use a different sensor for dehumidification
control. See “Humidification control”
beginning on page 130.
Note: Humidity sensing cannot be
averaged.
8030 What Terminals are
Wired to the
Humidifier?
None
U1
U2
U3
Thermostat
defaults to the
next unused
universal
terminal (U1,
U2, U3).
Both No Number of Universal Outputs:
THX9321 Thermostat: U1 and U2 terminals
Equipment Interface Module (EIM): U1, U2
and U3 terminals
U1, U2, U3 are dry contacts that require
power. See “Wiring IAQ Equipment or a
Heat/Cool Stage to the Universal
Terminals” beginning on page 149.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes