THX9321 & THX9421 Product Data

Table Of Contents
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—02 58
9080 Dehumidification
Control
Basic
Minimum On Time
High Humidity Comfort Reset
High Humidity Comfort Reset with
Minimum On Time
Reheat
Reheat with Minimum On Time
Basic Commercial No See “Dehumidification - Commercial”
beginning on page 109.
9090 Dehumidification
Minimum On Time
5 to 15 minutes
10 minutes Commercial No This option ensures that the compressor
runs long enough to effectively reduce
humidity when the cooling equipment is
cycled on. The compressor will run for the
“minimum on time” you set until the
desired humidity level is reached.
9100 High Humidity
Comfort Reset
Setting
1° F to 5° F
2° F Commercial No The thermostat uses the cooling system to
reduce humidity by lowering the
temperature up to 5° F below the current
cool setpoint until the desired humidity
level is reached.
The thermostat keeps the temperature
below the cooling setpoint until the desired
humidity level is reached.
9120 System Modes
Allowing
Dehumidification
Check box on screen for each:
Heat
Cool
Off
Cool
Default varies
based on
heating/cooling
equipment
selected
Both No This ISU is only displayed when ISU 9000
Dehumidification Equipment is set to
Dehumidifier.
Click boxes on screen to select which
system modes allow dehumidification. If a
box is NOT checked, the thermostat will
NOT allow dehumidification to operate in
that mode.
Heat: Includes Heat, Emergency Heat and
Auto. If the system is in Auto mode, the
thermostat will allow dehumidification if
the last call was for heat.
Cool: Includes Cool and Auto. If the system
is in Auto mode, the thermostat will allow
dehumidification if the last call was for
cool.
Off: The thermostat will allow
dehumidification when the system setting
is Off.
See “Dehumidification - Residential”
beginning on page 105 or
“Dehumidification - Commercial”
beginning on page 109.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes