THX9321 & THX9421 Product Data

Table Of Contents
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—02 66
13130 Allow Cool Delta T
Diagnostics when
Indoor
Temperature is
[Indoor
Temperature
Range]
Minimum Setting
No Limit
35° F to 115° F (in 5° F
increments)
No Limit
(Always)
Both Yes This ISU only applies to Cooling.
This ISU is only displayed when ISU 13015
Set Advanced Diagnostic Options is set to
Yes.
The thermostat monitors Delta T of the
system ONLY when the indoor temperature
is within a certain range. Set to No Limit to
monitor Delta T during all indoor
temperature conditions.
13130
Maximum Setting
No Limit
40° F to 120° F (in 5° F
increments)
No Limit
(Always)
Both Yes
13140 Allow Cool Delta T
Diagnostics when
Indoor Humidity is
[Indoor Humidity
Range]
Minimum Setting
No Limit
0% to 95% (in 5% increments)
No Limit
(Always)
Both Yes This ISU only applies to Cooling.
This ISU is only displayed when ISU 13015
Set Advanced Diagnostic Options is set to
Yes.
The thermostat monitors Delta T of the
system ONLY when the indoor humidity is
within a certain range. Set to No Limit to
monitor Delta T during all indoor humidity
conditions.
13140
Maximum Setting
No Limit
5% to 100% (in 5% increments)
No Limit
(Always)
Both Yes
13150 Allow Cool Delta T
Diagnostics when
Outdoor
Temperature is
[Outdoor
Temperature
Range]
Minimum Setting
No Limit
-50° F to 135° F (in 5° F
increments)
No Limit
(Always)
Both Yes This ISU only applies to Cooling.
This ISU is only displayed when ISU 13015
Set Advanced Diagnostic Options is set to
Yes.
The thermostat monitors Delta T of the
system ONLY when the outdoor
temperature is within a certain range. Set
to No Limit to monitor Delta T during all
outdoor temperature conditions.
13150
Maximum Setting
No Limit
-45° F to 140° F (in 5° F
increments)
No Limit
(Always)
Both Yes
13160 Allow Cool Delta T
Diagnostics when
Outdoor Humidity
is [Outdoor
Humidity Range]
Minimum Setting
No Limit
0% to 95% (in 5% increments)
No Limit
(Always)
Both Yes This ISU only applies to Cooling.
This ISU is only displayed when ISU 13015
Set Advanced Diagnostic Options is set to
Yes.
The thermostat monitors Delta T of the
system ONLY when the outdoor humidity is
within a certain range. Set to No Limit to
monitor Delta T during all outdoor humidity
conditions.
13160
Maximum Setting
No Limit
5% to 100% (in 5% increments)
No Limit
(Always)
Both Yes
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes