4.2 Ethernet Port
Table 3 - Ethernet Port
Speeds
10 BaseT Ethernet (10-Mbps)
100 BaseTx Fast Ethernet (100-Mbps)
Modes
Half or Full Duplex
Auto - Negotiation
Both 10/100-Mbps and Half/Full Duplex
Connector Type
Shielded RJ-45
Cable Type (Recommended)
CAT5 (or better) UTP
Port
Auto MDI/MDI-X
4.3 External DIP Switch settings
4.4 CAN Network Port and wiring 4.5 Power port and wiring
Table 2 - Ports and Functions
Functions
Port 1 (MJ1)
Port 2 (MJ2)
RS-232
!
!
Hardware Handshaking
!
X
Programming
!
X
Ladder function controlled
!
!
Serial Downloadable
Protocols
!
!
RS 485 Half duplex
!
!
RS485 Full duplex
X
!
NET 1 Port Pin Assignments
Pin
Signal
Signal Description
Direction
1
V-
CAN Ground
-
2
CN_L
CAN Data Low
In/Out
3
SHLD
Shield Ground
-
4
CN_H
CAN Data High
In/Out
5
NC
No Connect
-
Primary Power Port Pins
Pin
Signal
Description
1
Ground
Frame Ground
2
V-
Input Power Supply Ground
3
V+
Input Power Supply Voltage
As seen when looking at the side of the RX371 unit:
The DIP Switches are used for
termination of the RS-485 ports. The
RX371 is shipped un-terminated.
To terminate, select one of the DIP
Switches and configure it based
upon the option that is desired.
MJ1
On
Off
On
Off
On
Off
MJ2
SW1
ON enables MJ2 RS485 port termination (121 ohms)
OFF disables MJ2 RS485 port termination.
SW2 & SW3
ON places MJ2 RS485 port in half-duplex mode.
OFF places MJ2 RS485 port in full-duplex mode.
SW4
ON enables MJ1 RS485 port termination (121 ohms)
OFF disables MJ1 RS485 port termination.
CAN Connector
Use the CAN Connector when
using CsCAN network.
Torque rating 4.5 7 Lb-In
(0.50 0.78 N-m)
Power Connector
Power Up:
Connect to Earth Ground.
Apply 10 - 30 VDC.
Screen lights up.
Torque rating 4.5 7 Lb-In
(0.50 0.78 N-m)