Manual

MAN0265-09 10 NOV 2006 PAGE 1
HSC600
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
This datasheet also covers products starting with IC300.
This product also has a detailed supplement (SUP0265) available.
1 SPECIFICATIONS
INPUT HSC600
HSC600
Inputs per
Module
8
Commons per Module 1
Zero
Crossing
TTL /
5 VDC
12
VDC
24
VDC
Input Type Positive Logic
Peak Voltage 35 VDC Max.
+ 0.1
+ 2
+ 8
+ 16
Input Impedance 10 K
Programmable
Input Voltage
Ranges
ON Voltage
Level
OFF Voltage
Level
- 0.1 + 0.8 + 4 + 8
Input Filter
500 KHz, 50 KHz,
5 KHz
OUTPUT HSC600
HSC600
Outputs per Module 8 Output Protection Short Circuit
Commons per Module 1
Maximum Leakage Current
100 µA
Operating Voltage 5–35 VDC Maximum Inrush Current 600 mA. per channel
Output Type
Sinking / 10 K Pull-Up
Negative Logic
Minimum Load None
Peak Voltage
35 VDC Max.
OFF to ON Response
0.3 µS.
Output Characteristics
Current Sinking
ON to OFF Response
2 µS.
ON Voltage Level
1.5 VDC Max. @ 500 mA
0.7 VDC Max. @ 250 mA
Maximum Load Current per
Output
0.5 A
General Specifications
Required Power
(Steady State)
0.29 W (12.43 mA @
24 VDC)
Relative Humidity 5–95% Non-condensing
Operating
Temperature
0°–60° Celsius
Required Power (Inrush)
0.44 W (18.4 mA @
24 VDC)
Weight 9.5 oz. (270 g)
CE See Compliance Table at http://www.heapg.com/Support/compliance.htm
UL
Operating Temperature Code T4A;
See Compliance Table at http://www.heapg.com/Support/compliance.htm
High Speed Counter
HE800HSC600 / HE-HSC600*
High Speed Counter Inputs
Sinking Pulse Outputs
* HE- denotes plastic case.

Summary of content (8 pages)