User guide

MAN0897-01 Specifications / Installation
______________________________________________________________________________________________________
03/02/2009 Page 1 of 2 ECN # 952
1 GENERAL SPECIFICATIONS
General Specifications
Storage
Temperature
-25° to 70° C
Operating
and Storage
Humidity
5 to 95% Non-condensing
Operating
Temperature
0° to 55° C
Pollution
degree
2 or lower
Atmosphere
Free from corrosive
gases and
excessive dust
Cooling
method
Self-cooling
Vibration
Occasional Vibration
Frequency Acceleration Amplitude
Sweep
Count
10 f < 57 Hz
- 0.075 mm
57 f 150 Hz
9.8 m/s
2
{1G} -
10 times in each
direction for
X,Y,Z
Continuous Vibration
Frequency Acceleration Amplitude
Sweep
Count
10 f < 57 Hz
- 0.035 mm
57 f 150
Hz
4.9 m/s
2
{0.5G} -
10 times in each
direction for
X,Y,Z
Shocks
Maximum shock
acceleration
147 m/s
2
{15G}
Duration Time 11 ms.
Pulse Wave Half sine wave pulse (3 times in each of X, Y, Z directions)
Noise Immunity
Square wave
impulse noise
AC: ± 1,500VDC
DC: ± 900VDC
Electrostatic
Discharge
Voltage: 4kV (contact discharge)
Radiated
electromagnetic
field
27 – 500MHz, 10V/m
Severity
level
All power
modules
Digital I/Os
(Ue 24V)
Digital I/Os
(Ue < 24 V)
Analog I/Os
Communication
I/Os
Fast Transient
Burst Noise
Voltage 2 kV 1 kV 0.25 kV
2 DIMENSIONS
a. DQM602
SmartStix
TM
HE559DQM602
Remote I/O for the OCS/RCS Family
16 Rela
y
Out
p
uts
(
250VAC
,
30VDC
,
2.0A
)
b. Terminal Strips
3 NETWORK CABLE
For detailed wiring information, refer to the Control Station Hardware Manual. A
handy checklist is provided that covers panel box layout requirements and minimum
clearances. See Section 10 for our web address.
Pin Description
RED 1 V+
WHT 2 CAN_H
NC 3 No Connection
BLU 4 CAN_L
BLK 5 V-
4 ID SWITCHES (SETTING CSCAN NETWORK IDs)
CsCAN Network IDs are set using the hexadecimal number system from 01 to FD. The
decimal equivalent is 1-253. Refer to Section 8, which shows the decimal equivalent of
hexadecimal numbers. Set a unique Network ID by inserting a small Phillips screwdriver
into the two identical switches. Note: The CsCAN Baud Rate for SmartStix I/O is fixed at
125KBaud.
5 LEDs
a. Diagnostic LED Indicators
Diagnostic LED State Meaning
Solid Red RAM or ROM test failed
Blinking Red I/O test failed
Blinking Green Module is in power-up state
MS: (indicates fault status of
Module )
Solid Green Module is running normally
Solid Red Network Ack or Dup ID test failed
Blinking Red Network ID test failed
Blinking Green
Module is in Life Expectancy default
state
NS: (indicates fault status of
Network)
Solid Green Network is running normally
b. Status LED Indicators
The Power Status LED illuminates Red when power is applied to the module. There are
I/O Status LED indicators for each of the Digital I/O points, which illuminate Red when an
I/O point is ON.
1.87
0.31
HE559-With Removable
Strip
6.95 [176.5mm]
6.61 [167.9mm]
1.62 [41.1mm]
0.18 [4.6mm]
1.97 [49.9mm]
Close-up of Switches
006DIM001
Use this switch to set
the Low Digit – has
an x1 multiplier.
Use this switch to set the
High Digit –has an x16
multiplier.
I/O Status LEDs
Power and Diagnostic
LEDs
INPUT
S
LO (x1)HI (x16)
MS
NS PWR
SmartStix I/O
2 1 4 5 6 7 8 113 9 12 13 14 15 1610
INPUTS
LO (x1)HI (x16)
MS
NS PWR
SmartStix I/O
2 1 4 5 6 7 8 113 9 12 13 14 15 1610
Recommended Cable
Thick:
(Max Distance =
500m)
Belden 3082A
Thin:
(Max Distance =
100m)
Belden 3084A