MIX577 07 APR 2006 Analog I/O Module HE559MIX577 4 Input Channels 2 Output Channels ±5V / ±10V / 4-20mA / ±20mA CsCAN Page 1 SmartStix Refer to SmartStix Analog Programming Guide (MAN0703) at www.HornerOCS.com.
Page 2 07 APR 2006 MIX577 Vibration Occasional Vibration Frequency 10 ≤ f < 57 Hz 57 ≤ f ≤ 150 Hz Acceleration Amplitude - 0.075 mm 9.8 m/s2 {1G} - Sweep Count 10 times in each direction for X,Y,Z Continuous Vibration Frequency Acceleration Amplitude 10 ≤ f < 57 Hz - 0.035 mm 57≤ f ≤ 150 Hz 4.9 m/s {0.5G} Sweep Count 10 times in each direction for X,Y,Z 2 - Shocks Maximum shock acceleration 2 147 m/s {15G} Duration Time Pulse Wave 11 ms.
Page 3 3 07 APR 2006 MIX577 WIRING MIX577 NC NC FT FT FT NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC +/- 10V C I1v +/20mA +/20mA +/- 20mA LOAD NC FT FT NC NC NC NC NC NC NC NC C I2v I2i I4v I4i C Q2v Q2i I2i C I4v I3v FT: Factory Test, Do Not Connect I4i I3i +/- 10v LOAD NC FT NC NC NC NC NC NC NC NC NC I1v I1i C I3v I3i Q1v Q1i C I2v I1i +/- 10V 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 MIX577 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 Q
Page 4 4 07 APR 2006 MIX577 INTERNAL WIRING SmartStack Inputs I/O Connector 700KΩ Voltage Input + _ Field Side To Controller 300KΩ Current Input 6V 150Ω Isolated Common SmartStack Outputs I/O Connector Voltage Output Mode 100Ω - Field Side + 100Ω Current Output Isolated Common Mode < From Controller
Page 5 5 07 APR 2006 MIX577 CHANNEL MODE, PROGRAMMABLE FILTER, AND OUTPUT DEFAULT CONFIGURATION The network supplies configuration information to the HE550MIX577 in the Consumed Directed Digital Data Words sent to the HE550MIX577. In the first word, the low 12 bits, 1 through 12, are channel mode bits. A low mode bit selects ±10V and a high mode bit selects ±20mA. The next three bits, 13 through 15, are input digital filter time constant codes and the high bit, 16, is an adaptive filter enable bit.
Page 6 07 APR 2006 MIX577 Bits 9 through 12 of the 5th configuration word control the behavior of the analog outputs when network communication is lost. The bit to channel correspondence is the same as for the mode and scale bits. If the corresponding bit is set, the outputs hold the last state. If the corresponding bit is cleared, the outputs are set to the respective value supplied to the HE550MIX577 in the second four words of the Consumed Directed Analog Data sent by the OCS.
Page 7 7 07 APR 2006 MIX577 SETTING ID SWITCHES CsCAN Network IDs are set using the hexadecimal number system from 01 to FD. The decimal equivalent is 1-253. Refer to following Conversion Table, which shows the decimal equivalent of hexadecimal numbers. Set a unique Network ID by inserting a small Phillips screwdriver into the two identical switches.
Page 8 Dec 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 07 APR 2006 Hex HI LO 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 1 2 3 4 5 6 7 8 9 A B C D E F 0 1 2 3 4 5 6 7 8 9 A B C D E F 0 1 2 3 4 5 6 7 8 9 A B C D E F 0 1 2 3 4 5 Dec 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89
Page 9 8 07 APR 2006 MIX577 LEDS SmartStix I/O Modules provide diagnostic and status LED indicators. a. Diagnostic LED Indicators Diagnostic LED MS (Module Status) NS (Network Status) State Solid Red Blinking Red Blinking Green Solid Green Solid Red Blinking Red Blinking Green Solid Green Meaning Initializing I/O test failed, internal hardware fault Module is in power-up state * Module is running normally Network Ack or Dup ID test failed ** Network ID test failed: ID not in the range of 1..
WHT RED SHIELD SHIELD VCN_L CN_H V+ WHT RED WHT RED BLK BLU BLK BLU 121Ω V+ VCN_L BLK BLU SHIELD CN_H MIX577 CN_H V+ SHIELD VCN_L CN_H V+ WHT RED SHIELD 121Ω BLK BLU SHIELD 07 APR 2006 VCN_L Page 10 SHIELD + 12-25VDC 001CAN002 CAN Wiring Note: 12 - 24VDC must be supplied to the network. 10 INSTALLATION / SAFETY When found on the product, the following symbols specify: Warning: Consult user documentation. Warning: Electrical Shock Hazard.
Page 11 07 APR 2006 MIX577 Adhere to the following safety precautions whenever any type of connection is made to the module. • • • • • • • • 11 Connect the green safety (earth) ground first before making any other connections. When connecting to electric circuits or pulse-initiating equipment, open their related breakers. Do not make connections to live power lines. Make connections to the module first; then connect to the circuit to be monitored.
Page 12 12 07 APR 2006 TECHNICAL SUPPORT For assistance and manual updates, contact Technical Support at the following locations: North America: (317) 916-4274 www.heapg.com email: techsppt@heapg.com Europe: (+) 353-21-4321-266 www.horner-apg.com email: techsupport@hornerirl.