1 SPECIFICATIONS
Table 1 – OCS100 /OCS110 Specifications
OCS100 OCS110
64K 128K
64K
128K
Memory
Ladder Memory
Screen Memory
Register Memory
8K
24K
Ladder Execution
Typical Execution Speed
0.7 ms. per 1K of boolean logic.
Primary Power Range*
10-30VDC
Primary Serial
Standard 9 pin RS-232 for programming, monitoring, and network
administration. Modbus/RTU Master, Slave, ASCII Send and Receive, and
CsCAN Serial also supported.
CAN Power Range 12 – 25 VDC
CAN Power Current 75mA maximum
CAN Network CsCAN Network / DeviceNet Slave
Input / Output
Local (All Modules): Maximum of four (4) SmartStack Modules per OCS
Remote (OCS110 / 210/ 250 / or RCS250 Modules):
In addition to 4 local I/O modules, up to 20 remote SmartStack I/O Modules
can be connected to an OCS or RCS using five Fiber Optic Bases, which each
contain four I/O slots.
Keypad
Faceplate made of Autotex® polyester by Autotype®. The material is
resistant to most corrosive substances found in industrial environments. The
material also holds up well in most industrial conditions. If used outdoors, the
material can yellow or crack.
UL Class 1, Groups A, B, C, D, Division 2
CE Yes
Operating Temperature
0°C to +60°C **
Typical Power Draw *
160mA @ 24VDC
Inrush Current *
200mA @ 24VDC for 70mS
Humidity 5% to 95% non-condensing
NEMA Standard
NEMA 4, 12
(Note: UL NEMA 4, 4x, 12 available as an option for OCS100 / 110, OCS200
/ 210. This option is highly recommended for wash down environment.)
Height 5.05” (128.24 mm)
Width 9.05” (229.84 mm)
Mounting Depth 2.00” (50.80 mm)
User Keys 17
Keypad 10 user-programmable keys + Shift, Esc, Enter and 4 direction keys
Display 2x20 LCD w/backlight; 4.84w x 8.06h mm characters
* These specifications are for OCS products without any SmartStack I/O Modules attached. The specifications for the
SmartStack Modules can be found in the applicable SmartStack Data Sheets.
**
Although the OCS withstands the temperature range of 0°C to +60°C, such temperatures may decrease the life of the
display. The recommended rating is 0°C to +50°C.
Operator Control Station
HE500OCS100 / OCS110
Products Specifications and Installation Data

Summary of content (6 pages)