Instruction Manual
MAN0886-04-EN       Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________ 
3/2/2010      Page 6 of 6        #1037 
6  Filter 
Filter Constant sets the level of digital filtering according to the following chart. 
Digital Filtering. The illustration above demonstrates the effect of digital filtering 
(set with Filter Constant) on module response to a temperature 
change. 
7  I/O Register Map 
Registers 
Description 
%I1 to %I24  Digital Inputs 
%I32  Output Fault 
%I25 to %I31  Reserved 
%Q1 to %Q16  Digital outputs 
%Q17  Clear HSC1 accumulator to 0 
%Q18 
Totalizer: Clear HSC2 
Quadrature 1-2: Accumulator 1 
Reset to max – 1 
%Q19  Clear HSC3 Accumulator to 0 
%Q20 
Totalizer: Clear HSC4 
Quadrature 3-4: Accumulator 3 
Reset to max – 1 
%Q21 to %Q32  Reserved 
%AI1 to %AI4  Analog inputs 
%AI5, %AI6  HSC1 Accumulator 
%AI7, %AI8  HSC2 Accumulator 
%AI9, %AI10  HSC3 Accumulator 
%AI11, %AI12  HSC4 Accumulator 
%AQ1, %AQ2  PWM1 Duty Cycle 
%AQ3, %AQ4  PWM2 Duty Cycle 
%AQ5, %AQ6  PWM Prescale 
%AQ7, %AQ8  PWM Period 
%AQ9 to %AQ14  Analog outputs 
Note: Not all XL6 units contain the I/O listed in this table. 
Registers  PWM  HSC  Stepper 
%AQ1 
Start 
Frequency 
%AQ2 
PWM1 Duty 
Cycle 
(32 bit) 
HSC1 
Preset 
Value 
Run 
Frequency 
%AQ3 
%AQ4 
PWM2 Duty 
Cycle 
(32 bit) 
HSC2 
Preset 
Value 
Accel Count 
(32 bit) 
%AQ5 
%AQ6 
PWM Prescale 
(32 bit) 
Run Count 
(32 bit) 
%AQ7 
%AQ8 
PWM Period 
(32 bit) 
Decel Count 
(32 bit) 
%Q1      Run 
%I30  Ready/Done 
%I31 
Error 
9  Technical Support 
For assistance and manual updates, contact Technical Support at the following 
locations: 
North America: 
Tel: 317 916-4274 
Fax: 317 639-4279 
Web: http://www.heapg.com 
Email: techsppt@heapg.com 
Europe: 
Tel: +353-21-4321266 
Fax: +353-21-4321826 
Web: http://www.horner-apg.com 
Email: tech.support@horner-apg.com 
 All applicable codes and standards need to be followed in the installation of this product. 
 Adhere to the following safety precautions whenever any type of connection is made to the 
module: 
  Connect the  safety (earth)  ground on  the power  connector first  before  making any  other 
connections. 
 When connecting to electric circuits or pulse-initiating equipment, open their related breakers. 
 Do not make connections to live power lines. 
 Make connections to the module first; then connect to the circuit to be monitored. 
 Route power wires in a safe manner in accordance with good practice and local codes. 
  Wear  proper  personal  protective  equipment  including safety  glasses and  insulated  gloves 
when making connections to power circuits. 
 Ensure hands, shoes, and floors are dry before making any connection to a power line. 
 Make sure the unit is turned OFF before making connection to terminals. 
 Make sure all circuits are de-energized before making connections. 
 Before each use, inspect all cables for breaks or cracks in the insulation. Replace immediately 
if defective. 
• Use Copper Conductors in Field Wiring Only, 60/75° C 
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or Non-hazardous 
locations only 
WARNING – EXPLOSION HAZARD – Do not disconnect equipment unless power has been 
switched off or the area is known to be non-hazardous. 
AVERTISSEMENT - RISQUE D'EXPLOSION - AVANT DE DECONNECTOR L'EQUIPMENT, 
COUPER LE COURANT OU S'ASSURER QUE L'EMPLACEMENT EST DESIGNE NON 
DANGEREUX.
WARNING: To avoid the risk of electric shock or burns, always connect the safety (or earth) 
ground before making any other connections. 
WARNING: To reduce the risk of fire, electrical shock, or physical injury it is strongly 
recommended to fuse the voltage measurement inputs.  Be sure to locate fuses as close to the 
source as possible. 
WARNING: Replace fuse with the same type and rating to provide protection against risk of fire 
and shock hazards. 
WARNING: In the event of repeated failure, do not replace the fuse again as a repeated failure 
indicates a defective condition that will not clear by replacing the fuse. 
WARNING – EXPLOSION HAZARD – Substitution of components may impair suitability for 
Class I, Division 2 
AVERTISSEMENT - RISQUE D'EXPLOSION - LA SUBSTITUTION DE COMPOSANTS PEUT 
RENDRE CE MATERIAL INACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE 1, 
DIVISION 2 
WARNING - The USB parts are for operational maintenance only. Do not leave permanently 
connected unless area is known to be non-hazardous.
WARNING – EXPLOSION HAZARD - BATTERIES MUST ONLY BE CHANGED IN AN AREA 
KNOWN TO BE NON-HAZARDOUS 
AVERTISSEMENT - RISQUE D'EXPLOSION - AFIN D'EVITER TOUT RISQUE D'EXPLOSION, 
S'ASSURER QUE L'EMPLACEMENT EST DESIGNE NON DANGEREUX AVANT DE 
CHANGER LA BATTERIE
WARNING -
 Battery May Explode If Mistreated. Do Not Recharge, Disassemble or Dispose Of In 
Fire. 
WARNING:
 Only qualified electrical personnel familiar with the construction and operation of this 
equipment and the hazards involved should install, adjust, operate, or service this equipment. 
Read and understand this manual and other applicable manuals in their entirety before 
proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life. 
60
20
100
40
80
20
0
10
100
90
80
70
60
50
40
30
Scans
0
1 2 3 4 5
6
0 7
%
C
o
m
p
l
e
t
e
[
]
Filter
Constant
This device complies with part 15 of the FCC Rules. Operation is subject to the following two 
conditions: 
1.  This device may not cause harmful interference. 
2.  This device must accept any interference received, including interference that may 
cause undesired operation. 
Radiated Emission Compliance: For compliance requirement, a ferrite (Horner P/N FBD006 
supplied with the unit) needs to be placed on the AC/DC line with one loop. 
Warning: Consult 
user documentation. 
Warning: Electrical 
Shock Hazard. 
No part of this publication may be reproduced without the prior agreement and written permission of Horner APG, Inc. Information in this document is subject to change without 
notice.
8  Safety 
When found on the product, the following symbols specify: 