Manual
MAN0885-04-EN         Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________ 
3/2/2010       Page 1 of 6       #1037 
1  Specifications 
Specifications 
Digital DC Inputs 
Inputs per Module 
12 including 4 configurable 
HSC inputs 
Commons per Module  1 
Input Voltage Range  12 VDC / 24 VDC 
Absolute Max. Voltage  35 VDC Max. 
Input Impedance 
10 kΩ 
Input Current  Positive Logic  Negative Logic 
Upper Threshold  0.8 mA  -1.6 mA 
Lower Threshold  0.3 mA  -2.1 mA 
Max Upper Threshold  8 VDC 
Min Lower Threshold  3 VDC 
OFF to ON Response  1 ms 
ON to OFF Response  1 ms 
HSC Max. Switching Rate 
10 kHz Totalizer/Pulse, 
Edges 
5 kHz Frequency/Pulse, 
Width 
2.5 kHz Quadrature 
Digital Relay Outputs 
Outputs per Module  6 relay 
Commons per Module  6 
Max. Output Current per Relay  3 A at 250 VAC, resistive 
Max. Total Output Current  5 A continuous 
Max. Output Voltage  275 VAC , 30 VDC 
Max. Switched Power  1250 VA, 150 W 
Contact Isolation to XL6 
ground 
1000 VAC 
Max. Voltage Drop at Rated 
Current 
0.5 V 
Expected Life 
(See Derating section for 
chart.) 
No load: 5,000,000 
Rated load: 100,000 
Max. Switching Rate 
300 CPM at no load 
20 CPM at rated load 
Type  Mechanical Contact 
Response Time 
One update per ladder scan 
plus 10 ms 
Analog Inputs, Medium Resolution 
Number of Channels  4 
Input Ranges 
 0 - 10 VDC 
 0 – 20 mA 
4 – 20 mA 
Safe input voltage range  -0.5 V to +12V 
Input Impedance 
(Clamped @ -0.5 VDC to 12 
VDC) 
Current 
Mode: 
100 Ω 
Voltage 
Mode: 
500 k Ω 
Nominal Resolution  10 Bits 
%AI full scale  32,000 counts 
Max. Over-Current  35 mA 
Conversion Speed 
All channels converted once 
per ladder scan 
Max. Error at 25°C 
(excluding zero) 
*can be made tighter (~0.25%) 
by adjusting the digital filter 
setting to 3. 
4-20 mA  1.00% 
0-20 mA  1.00% 
 0-10 VDC  1.50%* 
Additional error for 
temperatures other than 25°C 
TBD 
Filtering 
160 Hz hash (noise) filter 
1-128 scan digital running 
average filter 
General Specifications 
Required Power 
(Steady State) 
500 mA @ 24 VDC 
Required Power 
(Inrush) 
30 A for 1 ms @ 24 VDC – DC Switched 
2.5 A for 4 ms @ 24 VDC - AC Switched 
Primary Power Range  10 – 30 VDC 
Relative Humidity  5 to 95% Non-condensing 
Clock Accuracy 
+/- 35 ppm maximum at 25° C 
(+/- 1.53 Minutes per Month) 
Operating Temperature 
-10°C to +60°C 
Terminal Type  Screw Type, 5 mm Removable 
Weight  26.5 oz. (.751 kg) 
CE 
UL 
USA: http://www.heapg.com/Pages/TechSupport/ProductCert.html 
Europe: http://www.horner-apg.com/en/support/certification.aspx 
Display Type  5.7” QVGA TFT 
Display Size  5.7” 
Display Screen 
Dimension 
320 x 240 
Display Memory  2.75 MB 
Display Life  Minimum 40000 hours (50% brightness, 25 deg C) 
User Keys  5 user-defined Function keys and a System Key 
Screens supported  1023 
Colors  32768/ 16 shade Grey scale (XL6M models only) 
Connectivity 
Serial Ports  2 Serial Ports – RS232 & RS485 
Ethernet  10/100-Mbps (XL6e models only) 
USB 
USB Networking Port for communication with PCs, flash device connectivity 
and programming Port 
Removable Media 
Removable Media for upto 2 GB of storage for programs, data logging or 
screen capture 
Smartstix  Remote IO modules communicating on CAN 
HE-XL102 / HE-XL1E2 / HE-XL1M2 
XL6/XL6M/XL6e OCS Models 
HE-XL102 / HE-XL1M2 / HEXT350C112 / HEXT280C112 
HE-XL1E2 / HEXT351C112 
12 Digital DC Inputs 
4 Analog Inputs (Medium Resolution) 
6 Digital Relay Outputs
Note: Highest usable frequency for PWM output is 65 KHz 