User guide
MAN0887-05-EN       Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________ 
3/2/2010       Page 7 of 8       #1037 
 6  I/O Register Map 
Registers 
Description 
%I1 to %I24  Digital Inputs 
%I32  Output Fault 
%I25 to %I31  Reserved 
%Q1 to %Q16  Digital outputs 
%Q17  Clear HSC1 accumulator to 0 
%Q18 
Totalizer: Clear HSC2 
Quadrature 1-2: Accumulator 1 Reset to 
max – 1 
%Q19  Clear HSC3 Accumulator to 0 
%Q20 
Totalizer: Clear HSC4 
Quadrature 3-4: Accumulator 3 Reset to 
max – 1 
%Q21 to %Q32  Reserved 
%AI1 to %AI4  Analog inputs 
%AI5, %AI6  HSC1 Accumulator 
%AI7, %AI8  HSC2 Accumulator 
%AI9, %AI10  HSC3 Accumulator 
%AI11, %AI12  HSC4 Accumulator 
%AQ1, %AQ2  PWM1 Duty Cycle 
%AQ3, %AQ4  PWM2 Duty Cycle 
%AQ5, %AQ6  PWM Prescale 
%AQ7, %AQ8  PWM Period 
%AQ9 to %AQ14  Analog outputs 
Note: Not all XL6 units contain the I/O listed in this table. 
Registers  PWM  HSC  Stepper 
%AQ1  Start Frequency 
%AQ2 
PWM1 Duty Cycle 
(32 bit) 
HSC1 
Preset 
Value 
Run Frequency 
%AQ3 
%AQ4 
PWM2 Duty Cycle 
(32 bit) 
HSC2 
Preset 
Value 
Accel Count (32 
bit) 
%AQ5 
%AQ6 
PWM Prescale 
(32 bit) 
Run Count (32 
bit) 
%AQ7 
%AQ8 
PWM Period 
(32 bit) 
Decel Count (32 
bit) 
%Q1      Run 
%I30  Ready/Done 
%I31 
Error 
 7  Digital Filtering for Analog Inputs 
The digital filter is updated once per conversion. It is an “IIR” running average filter that emulates a simple 
RC filter. The equivalent time constant is determined by the Filter Constant and the sum of the conversion 
times for the two channels. The Filter Constant determines the weight given to the most recent 
conversion. The following table lists the equivalent time constant for the three possible total conversion 
times, which are dependent upon the two input mode selections. This filter delay is in addition to the PLC 
scan delay. 
Equivalent RC Time Constant in Seconds 
(Nominal time to reach 63% of final value.)
  Total Conversion Time in Seconds 
Filter Constant  0.03  0.09  0.13 
0*  0.03*  0.09*  0.13* 
1  0.07  0.18  0.27 
2  0.13  0.35  0.53 
3  0.27  0.71  1.07 
4  0.53  1.41  2.13 
5  1.07  2.83  4.27 
6  2.14  5.65  8.54 
7  4.28  11.30  17.08 
* No filter delay, reading is unfiltered conversion value 
 8  Thermocouple Grounding Schemes 
Ungrounded Thermocouples 
Alternate Shield Connection for 
Ungrounded Thermocouples.
Ungrounded Thermocouples 
Preferred Shield Connection for 
Ungrounded Thermocouples.
Grounded Thermocouples 
Field Ground Potential Less Than 
Seven Volts AC 
Typical Shield Connection for 
Grounded Thermocouples
Grounded Thermocouples 
Field Ground Potential Less Than 
Seven Volts AC 
Shields Connected at One End Only 
May be Used to Reduce Noise 
Grounded Thermocouples May Use 
the Ungrounded Thermocouple Shield 
Connections if the Shield is not 
Grounded at the Field End
Note: The examples for thermocouple grounding schemes above are generic illustrations. The 
XL6 model XL105 has two thermocouple inputs. 








