Owner manual

Specifications/Installation
MAN0971-02-EN
Cutout tolerance to meet NEMA standards
is ±0.005” (0.1mm). Max. Panel Thickness is 5mm.
XL7 OCS Datasheet for
HE-XW1E0, HE-XW1E2, HE-XW1E3, HE-XW1E4, HE-XW1E5
HEXT391C100, HEXT391C112, HEXT391C113, HEXT391C114, HEXT391C115
1. Specifications
2. Dimensions & Panel Cutout
General Specifications
Control & Logic Specifications
Required Power
(Steady state)
170mA @ 24VDC Control Language Support
Advanced Ladder Logic
Full IEC 1131-3 Languages
Required Power
(Inrush)
7A for <1 ms @ 24 VDC
DC Switched
Logic Program Size
& Logic Scan Rate
1MB, maximum
0.013mS/K
Primary Power Range
1030VDC
Online Programming Changes
Supported in Advanced Ladder
Relative Humidity
5 to 95% Non-condensing
I/O Support
Digital Inputs
2048
Clock Accuracy
+/- 20 ppm maximum at 25
°
C
(+/- 1 Minutes per Month)
Digital Outputs
2048
Analog Inputs
512
Surrounding Air Temp
-40°C to +60°C
Analog Outputs
512
Storage Temp
-40°C to +60°C
General Purpose Registers
50,000 (words) Retentive
16,384 (bits) Retentive
16,384 (bits) Non-retentive
Weight
2lb. (without I/O)
UL / CE
Display Specifications
Connectivity
Display Type 7” TFT Transmissive Color
Serial Ports
1 RS-232 & 1 RS-485 on first Modular Jack (MJ1/2)
1 RS-232 or 1 RS-485 on second Modular Jack (MJ3)
Resolution
800x480
USB mini-B
USB 2.0 (480MHz) Programming & Data Access
Color
16-bit (65,535)
USB A
USB 2.0 (480MHz) for USB FLASH Drives (2TB)
Screen Memory
27 MB
CAN
Remote I/O, Peer-to-Peer Comms, Cscape
User-Programmable Screens 1023 Ethernet
10/100 Mb (Auto-MDX), Modbus TCP C/S, HTTP, FTP,
SMTP, Cscape, Ethernet IP
Backlight
LED 50,000 hour life
Remote I/O
SmartRail, SmartStix, SmartBlock, SmartMod
Screen Update Rate
User Configurable within the scan time.
(perceived as instantaneous in many cases)
Removable
Memory
MicroSD, support for 32GB max.
Application Updates, Datalogging, more
Input / Output Specifications
Model DC In
DC
Out
Relays HS In HS Out mA/V In
mA/V
RTD/Tc
mA/V
Out
High-Speed Counters
Number of Counters
2
Model 2
12
6
4
4
Maximum Frequency
500 kHz each
Model 3
12
12
4
2
2
Accumulator Size
32-bits each
Model 4
24
16
4
2
2
Modes Supported
Model 5
12
12
4
2
2
2
Totalizer
Quadrature
There are 4 high-speed inputs of the total DC Inputs. There are 2 high-speed outputs of the total DC
outputs. Model 2, 3 & 4 feature 12-bit Analog I/O. Model 5 features 14/16-bit Analog I/O. High-speed
Outputs can be used for PWM and Pulse Train Outputs, currently limited to <65kHz.
Pulse Measurement
Frequency
Measurement
2 Position Controlled Outputs
1 ON/OFF Setpoint per Output
Page 1 of 7