User Manual
    XL7 User Manual 
3.6  Factors Affecting Panel Layout Design and Clearances 
The designer of a panel layout needs to assess the requirements of a particular system and to consider 
the following design factors. 
3.6.1  Clearance / Adequate Space  
Install devices to allow sufficient clearance to open and close the panel door. 
Table 3.1 – Minimum Clearance Requirements for Panel Box and Door 
Minimum Distance between  
base of device and sides of cabinet 
2 inches (50.80mm) 
Minimum Distance between  
base of device and wiring ducts 
1.5 inches (38.10mm) 
If more than one device installed in panel box (or 
on door): Minimum Distance between bases of 
each device 
4 inches between bases of each device (101.60mm) 
When door is closed: 
Minimum distance between device and closed 
door (Be sure to allow enough depth for the OCS.) 
2 inches (50.80mm) 
3.6.2  Grounding  
Panel box: The panel box must  be properly connected to earth ground to provide a good common 
ground reference.  
Panel door: Tie a low impedance ground strap between the panel box and the panel door to ensure that 
they have the same ground reference. 
3.6.3  Temperature / Ventilation 
Ensure that the panel layout design allows for adequate ventilation and maintains the specified ambient 
temperature range. Consider the impact on the design of the panel layout if operating at the extreme 
ends of the ambient temperature range. For example, if it is determined that a cooling device is 
required, allow adequate space and clearances for the device in the panel box or on the panel door. 
3.6.4  Orientation 
When panel-mounted, there are no orientation restrictions on the XL7 OCS.  
Warning: It is important to follow the requirements of the panel manufacturer  
and to follow all applicable electrical codes and standards. 
Warning: Be sure to meet the ground requirements of the  
panel manufacturer and also meet applicable electrical codes and standards. 
Page 19 of 110 










