NOTE: Setting the PLC mode to stop while the stepper is in operation causes the stepper output to 
immediately drop to zero and the current stepper count to be lost. 
NOTE: The stepper output level may cause damage or be incompatible with some motor drive inputs. 
Consult drive documentation to determine if output level and type is compatible. 
11.6  PWM Functions Register Map 
The register assignments for the high speed I/O can be moved via a setting in Cscape. The values shown 
are the DEFAULT values and may not match the same starting point as the values shown below. 
Table 11.3 – PWM Functions Register Map 
Register 
PWM 
Stepper 
%AQ421-422 
PWM 1 Duty Cycle (32-bit) 
Start Frequency – Stepper 1 
%AQ423-424 
PWM 1 Frequency 
Run Frequency – Stepper 1 
%AQ425-426 
Acceleration Count – Stepper 1 
%AQ427-428 
Run Count – Stepper 1 
%AQ429-430 
Deceleration Count – Stepper 1 
%AQ431-432 
PWM 2 Duty Cycle (32-bit) 
Start Frequency – Stepper 2 
%AQ433-434 
PWM 2 Frequency 
Run Frequency – Stepper 2 
%AQ435-436 
Acceleration Count – Stepper 2 
%AQ437-438 
Run Count – Stepper 2 
%AQ439-440 
Deceleration Count – Stepper 2 
%Q1 
Digital Out – Stepper 1 
%Q2 
Digital Out – Stepper 2 
%I1617 
Ready/Done – Stepper 1 
%I618 
Error – Stepper 1 
%I1619 
Ready/Done – Stepper 2 
%I620 
Error – Stepper 2 
11.7  PWM Examples  
Example 1 
Duty Cycle 
Frequency 
To get a 50% Duty Cycle @ 10 kHz 
waveform on PWM1: 
Set %AQ421-422 = 16,000  Set %AQ423-424 = 10,000 
Example 2 
Duty Cycle 
Frequency 
To get a 50% Duty Cycle on PW1 and 
90 % Duty Cycle on PWM2 @ 1 kHz 
waveform: 
Set %AQ421-422 = 16,000 
Set %AQ431-432 = 28,800 
(duty cycle (32000 * 0.9)) 
Set %AQ423-424 = 1,000 
Set %AQ433-434 = 1,000 
Example 3 
Duty Cycle 
Frequency 
To turn PWM 1 output ON all the time 
Set %AQ421-422 = 32,000 
Set %AQ423-424 = Any Value 
Example 4 
Duty Cycle 
Frequency 
To turn PWM 1 output OFF all the 
time 
Set %AQ421-422 = 0  Set %AQ423-424 = Any Value 