Manual
MAN0852-02            21 AUGUST 2007             PAGE 3 
HE-XE102-10                         Specifications / Installation 
5  Wiring and Jumpers 
Wire according to the type of inputs / outputs used, and select the 
appropriate jumper option. 
5.1.  Wiring Examples 
J1 Orange 
Terminal 
Connector 
XE102 
Name 
I1  IN1 
I2  IN2 
I3  IN3 
I4  IN4 
I5  IN5 
I6  IN6 
I7  IN7 
I8  IN8 
H1  HSC1 /IN9 
0V  Ground 
A1  Thermistor 1 
A2  Thermistor 2 
A3  Analog IN3 
A4  Analog IN4 
0V  Ground 
J2 Black 
Terminal 
Connector 
XE102 
Name 
C6  Relay 6 COM 
R6  Relay 6 NO 
C5  Relay 5 COM 
R5  Relay 5 NO 
C4  Relay 4 COM 
R4  Relay 4 NO 
C3  Relay 3 COM 
R3  Relay 3 NO 
C2  Relay 2 COM 
R2  Relay 2 NO 
C1  Relay 1 COM 
R1  Relay 1 NO 
H4  HSC4 / IN12 
H3  HSC3 / IN11 
H2  HSC2 / IN10 
5.2  I/O Jumpers Settings (JP1 - JP2) 
5.3  External DIP Switch Settings (or Jumpers Settings) 
6  Derating 
Note:
 The Cscape Module Setup configuration must match the 
selected I/O (JP) jumper settings. 
001XLE026 
JP1 Digital DC In / HSC
Positive Negative 
Logic Logic 
Default 
A3 
A4
JP2 Analog In (A3 – A4) 
Current Voltage 
(20 mA) (10 V) 
Default 
Location of I/O jumpers (JP
) 
and wiring connectors 
(J1 and J2). 
I1
0V
001XLE036
12-24VDC
I1
0V
Positive Logic In Negative Logic In 
Positive Logic vs. Negative Logic Wiring 
The XLE can be wired for Positive Logic inputs or 
Negative Logic inputs. 
001XLE015
0V ON J1
12-24VDC
R2
C2
R3
C3
R6
C6
R4
C4
R5
C5
R1
C1
H4
H2
H3
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
XE102 J2 Black 
Positive Logic 
Digital In / Relay Out
Wiring Specifications 
For I/O wiring (discrete), use the 
following  wire type  or equivalent: 
Belden 9918, 18 AWG or larger. 
For  shielded  Analog
  I/O  wiring, 
use  the  following  wire  type  or 
equivalent:    Belden  8441,  18 
AWG or larger.
For  CAN  wiring,  use  the 
following  wire type  or equivalent: 
Belden 3084, 24 AWG or larger. 
Some XLes have jumpers to  set 
RS-
485  port  termination,  though 
most use DIP Switches. 
The  External  Jumpers  or  DIP 
Switches  are  used  for termination 
of  the  RS-
485  ports.  The XLE  is 
shipped un-terminated. 
To 
terminate,  select  one  of  the 
jumpers  shipped  with  the  product 
and insert it based upon the option 
that is desired or, select the switch 
and  configure  based  upon  the 
option that is desired. 
Factory Use
(default – none)
MJ2 Termination 
(default – none)
MJ1 Termination 
(default – none)
001XLE037
As seen when looking at the top of the XLE unit: Refer to 
Section 3 for the location of the External Jumpers. 
XE102 J1 Orange 
Positive Logic In 
Digital In / 
Analog In 
Note:  
When using JP2 (A3-A4), each 
channel can be independently 
configured. 
Note:  
Loop Power requirements are determined 
by the transmitter specification. 
XLE102 Relay Life Expectancy
0
10
20
30
40
1 2 3 4
Contact Current (A)
Operation 
(x10
4
)
Pin
MJ1 Pins  MJ2 Pins 
Signal  Direction  Signal  Direction 
8 
TXD  OUT  TXD  OUT 
7 
RXD  IN  RXD  IN 
6 
0 V  Ground  0 V  Ground 
5 
NC 
No 
Connect 
NC 
No 
Connect 
4 
RTS  OUT  TX-  OUT 
3 
CTS  IN  TX+  OUT 
2 
RX- / 
TX- 
IN / OUT  RX-  IN 
1 
RX+ / 
TX+ 
IN / OUT  RX+  IN 
1
8
Serial Communications: 
MJ1: (RS-232 / RS-485) Use for Cscape programming and 
Application
-Defined Communications. 
MJ2: (RS-232 / RS-485) Use for Application-Defined 
Communications. 
J1
JP2
JP1
J2
001XLE062
001XLE066
I1
I2
I3
I4
0V
A1
A2
0V
I5
I6
I7
I8
A3
A4
H1
001XLE067
12-24VDC
20mA LOOP
0-10VDC
T
T
001XLE037-R1
Factory Use
(default – none)
MJ2 Termination 
(default – none)
MJ1 Termination 
(default – none)