Owner's manual
MAN0848-02            21 August 2007              PAGE 1 
Specifications / Installation         HE-XE103-10
1  Specifications 
HE-XE103-10 Specifications 
Digital DC Inputs  XLE103-10 
Digital DC 
Outputs 
XLE103-10 
Inputs per Module 
12 including 4 configurable 
HSC inputs 
Outputs per 
Module 
12 including 2 configurable 
PWM outputs 
Commons per 
Module 
1 
Commons per 
Module 
1 
Input Voltage 
Range 
12 VDC / 24 VDC  Output Type  Sourcing / 10 K Pull-Down 
Absolute Max. 
Voltage 
35 VDC Max. 
Absolute Max. 
Voltage 
28 VDC Max. 
Input Impedance 
10 kΩ 
Output 
Protection 
Short Circuit 
Input Current 
Positive 
Logic 
Negative Logic 
Max. Output 
Current per 
point 
0.5 A 
Upper Threshold  0.8 mA  -1.6 mA 
Max. Total 
Current 
4 A Continuous 
Lower Threshold  0.3 mA  -2.1 mA 
Max. Output 
Supply Voltage 
30 VDC 
Max Upper 
Threshold 
8 VDC 
Minimum Output 
Supply Voltage 
10 VDC 
Min Lower 
Threshold 
3 VDC 
Max. Voltage 
Drop at Rated 
Current 
0.25 VDC 
OFF to ON 
Response 
1 ms 
Max. Inrush 
Current 
650 mA per channel 
ON to OFF 
Response 
1 ms  Min. Load  None 
HSC Max. 
Switching Rate 
10 kHz Totalizer/Pulse,Edges 
5 kHz Frequency/Pulse,Width 
2.5 kHz Quadrature 
OFF to ON 
Response 
1 ms 
Thermistor 
Inputs, Medium 
Resolution 
XLE103-10 
ON to OFF 
Response 
1 ms 
Number of 
Channels 
2 
Output 
Characteristics 
Current Sourcing (Pos logic) 
General Specifications 
Input Ranges 
Safe input voltage 
range 
Input Impedance 
(Clamped @ -0.5 
VDC to 12 VDC) 
10K OHM 
Thermistor 
Half Bridge 
9.59K ohm pulled up to 
4.8 VDC 
Required Power 
(Steady State) 
130 mA @ 24 VDC 
Required Power 
(Inrush) 
30 A for 1 ms @ 24 VDC 
Nominal Resolution 
%AI at 10K Ohm 
10 Bits 
15,008 counts 
Primary Power 
Range 
10 – 30 VDC 
Conversion Speed 
All channels converted once 
per ladder scan 
Relative Humidity 
5 to 95% Non-
condensing 
Max. Error at 25°C 
reading / ambient 
±0.5°F or ±0.3°C 
Using specified linearization 
in ladder program 
Operating 
Temperature 
0°C to +50°C 
Terminal Type 
Screw Type,5 mm 
Removable 
Additional error for 
reading / ambient 
temperatures other 
than 25°C 
TBD 
CE 
UL 
See Compliance Table at
http://www.heapg.com/Support/compliance.htm
Filtering 
160 Hz hash (noise) filter 
1-128 scan digital running 
average filter 
Weight  12.5 oz. (354.36 g) 
Clock Accuracy  +/- 7 Minute/Month at 20C 
Highest usable frequency for PWM output is 65 KHz 
2  Panel Cut-Out and Dimensions 
Note: Max. panel thickness: 5 mm. 
3  Ports / Connectors / Cables 
Note: The case of the XLE is black, but for clarity, it is shown in a 
lighter gray color. 
Want More Information?
To download the XLE User 
Manual (MAN0805), refer 
to Technical Support
 in this 
document. 
3
.
6
2
2
[
9
2
m
m
]
3.622 [92mm]
001XLE002
Refer to XLE User 
Manual (MAN0805) for 
panel box information 
and a handy checklist of 
requirements. 
Note: 
The tolerance to meet 
NEMA standards is 
± 0.005” (0.1 mm). 
To Remove Back Cover: 
Unscrew 4 screws located on 
the back of the unit. 
Lift lid. 
CAUTION: Do not overtighten 
screws when screwing the lid 
back on. 
001ACC009
Power Connector 
Power Up: 
Connect to Earth Ground.
Apply 10 
– 30 VDC. 
Screen lights up. 
CAN Connector 
Use the CAN Connector 
when usin
g CsCAN network. 
I/O Jumpers (Not Shown): I/O Jumpers (JP) are located 
internally. To access, remove back cover of unit. 
Wiring Connectors (J1 – J4), I/O Jumpers (JP1-3), and 
External Jumpers (RS-485) are described in the Wiring and 
Jumpers section of this document. 
XLE OCS Model: HE
-
XE103
-
10
12 Digital DC Inputs / 12 Digital Outputs 
2 10K Thermistor Inputs 
MJ1
(RS-232 / RS-485)
MJ2
(RS-232 / RS-485)
J1
I/O 
Jumper
Memory Slot
001XLE029-R2
 J2
I/O 
Jumper 
NET 1
(CsCAN)
Power
DIP
Switch