Owner's manual
PAGE 2              21 August 2007             MAN0848-02 
XLE103-10       Specifications / Installation 
Section 3 continued 
4  Wiring and Jumpers 
Wire according to the type of inputs / outputs used and select the appropriate jumper 
option. 
4.1.  I/O Jumper Setting (JP1) 
4.2.  External DIP Switch Settings (or Jumpers Settings) 
4.3.  Wiring Examples 
J1 
Orange 
XE103-10 
Name 
I1  IN1 
I2  IN2 
I3  IN3 
I4  IN4 
I5  IN5 
I6  IN6 
I7  IN7 
I8  IN8 
H1  HSC1 / IN9 
H2  HSC2 / IN10 
H3  HSC3 / IN11 
H4  HSC4 / IN12 
A1  Thermistor 1 
A2  Thermistor 2 
0V  Ground 
J2 
Black 
XE103-10 
Name 
0V  Ground 
V+  V+ * 
NC  No Connect 
Q12  OUT12 
Q11  OUT11 
Q10  OUT10 
Q9  OUT9 
Q8  OUT8 
Q7  OUT7 
Q6  OUT6 
Q5  OUT5 
Q4  OUT4 
Q3  OUT3 
Q2  OUT2 / PWM2 
Q1  OUT1 / PWM1 
V+* Supply for Sourcing Outputs 
8
1
Pin  MJ1 Pins  MJ2 Pins 
8 
TXD  OUT  TXD  OUT 
7 
RXD  IN  RXD  IN 
6 
0 V  Ground  0 V  Ground 
5 
NC 
No 
Connect 
NC 
No 
Connect 
4 
RTS  OUT  TX-  OUT 
3 
CTS  IN  TX+  OUT 
2 
RX- / 
TX- 
IN / 
OUT 
RX-  IN 
1 
RX+ / 
TX+ 
IN / 
OUT 
RX+  IN 
Note: The Cscape Module Setup configuration must match 
the selected I/O (JP) jumper settings. 
I1
0V
001XLE036
12-24VDC
I1
0V
Positive Logic In Negative Logic In 
Positive Logic vs. Negative Logic Wiring 
The XLE can be wired for Positive Logic inputs or 
Negative Logic inputs. 
Factory Use
(default – none)
MJ2 Termination 
(default – none)
MJ1 Termination 
(default – none)
001XLE037
As seen when looking at the top of the XLE unit. Refer to 
Section 3 for the location of the External Jumpers. 
Memory Slot: 
Uses  Removable  Memory 
for  data  logging,  screen 
captures, program loading and recipes. 
Horner Part No.: HE-MC1 
Serial Communications: 
MJ1: (RS-232 / RS-485) Use for Cscape programming and 
Application
-Defined Communications. 
MJ2: (RS-232 / RS-485) Use for Application-Defined 
Communications. 
Location of I/O jumper (JP1
) 
and wiring connectors 
(J1 & J2). 
Wiring Specifications 
For I/O wiring (discrete), use the 
following wire type or equ
ivalent:  
Belden 9918, 18 AWG or larger. 
For shielded Analog I/O wiring, 
use the following wire type or 
equivalent: Belden 8441, 18 
AWG or larger.
For CAN wiring, use the 
following wire type or equivalent:  
Belden 3084, 24 AWG or larger. 
Some XLes have jumpers to set RS-
485  port  termination,  tho
ugh  most 
use DIP Switches. 
The  External  Jumpers  or  DIP 
Switches  are  used  for termination  of 
the  RS-
485  ports.  The  XLE  is 
shipped un-terminated. 
To  terminate,  select  one  of  the 
jumpers shipped with the product and 
insert it based upon the option that is 
desired  or,  select  the  switch  and 
configure based upon the option that 
is desired. 
Negative Logic 
Positive Logic 
JP1 Digital DC Inputs
Default 
Q1
Q2
Q3
Q4
Q9
Q10
Q11
Q12
Q5
Q6
Q7
Q8
V+
0V
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
10 - 30VDC
Q13
001XLE024
LOAD
XE103-10 J2 Black 
Positive Logic 
Digital Out 
Note: The wiring examples show 
Positive Logic input wiring. 
I1
I2
I3
I4
0V
I5
I6
I7
I8
H1
001XLE061
12-24VDC
A1
A2
H2
H3
H4
T
T
J1 J2
JP1
001XLE060
XE103-10 J1 Orange 
Positive Logic 
Digital In 
001XLE037-R1
Factory Use
(default – none)
MJ2 Termination 
(default – none)
MJ1 Ter
mination 
(default – none)