Service Mnaual

Table Of Contents
12
A2. Thermistor/Control Module Sequence of Operation Flow Chart
1. Undercounter and Work Top: Refrigerator
1. Startup/Cool Down
2. Cool Down Achieved
Comp energized
ConFM energized
EvapFM energized
Comp de-energized
ConFM de-energized
EvapFM de-energized
CTh in control
Off cycle defrost
between run cycles
Refrigerator Sequence Flow Chart
2-min. Comp
on timer starts
2-min. Comp
off timer starts
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
EvapFM-evaporator fan motor
Power on
Red LED On
(5 sec. Delay)
Green LED Flashes
If Red LED ashes, check CTh
Green LED Flashes
If Red LED ashes, check CTh
CTh above setpoint
CTh cools to setpoint
CTh above
setpoint
Note: Delays
a) 2-min. minimum Comp on timer starts when Comp energizes.
b) 2-min. minimum Comp off timer starts when Comp de-energizes.
*
*
*