Ice Maker User Manual
36
IV. Service Diagnosis
A. Diagnostic Procedure
This diagnostic procedure is a sequence check that allows you to diagnose the electrical 
system and components. Before proceeding, check for correct installation, adequate 
water supply (minimum of 0 PSIG, maximum of 3 PSIG) and proper voltage per unit 
nameplate. Always choose a white neutral wire to establish a good neutral connection 
when checking voltages. LEDs on the control board correspond to the components as 
they energize. 
) Move the control switch to the "OFF" position, then turn off the power supply. Remove 
the upper and lower front panels. Conrm the power switch is in the "ON" position and 
the door switch is engaged.
) Turn on the power supply, then move the control switch to the "ICE" position. The 
"POWER" LED is on. The "POWER" LED will not come on if the door switch is not 
engaged.
3) Fill Cycle – The inlet water valve energizes. The reservoir lls. The lower oat switch 
closes. Nothing occurs at this time. The reservoir continues to ll until the upper oat 
switch closes, energizing the water control relay, which closes the low water safety 
circuit and de-energizes the inlet water valve. Diagnosis: Check that the inlet water 
valve lls the reservoir. If not, check for water supply line shut-off valve closed, clogged 
water lters, clogged inlet water valve screen, power circuit to the inlet water valve 
(power switch, door switch, power protect relay contacts, transformer, fuses, high 
pressure switch, bin control, control switch, oat switch, water control relay contacts), 
and the coil on the inlet water valve. Check that the inlet water valve shuts off when 
the upper oat switch closes. If not, check the oat switch, water control relay, and inlet 
water valve.
4) Ice Purge Cycle – "GM" LED is on (60 second short cycle protection). The 60 second 
timer starts, the water control relay remains energized, the gear motor, gear motor 
protect relay, heater control relay, and heater energize. Diagnosis: Check that the 
gear motor starts. If not, check that the water control relay is energized (inlet water 
valve should be closed). Check the low water safety circuit on the water control relay 
(terminals 4 and 6), check for 5/0V at the K connector "COM" terminal to neutral 
and "NO" terminal to neutral on the control board (see wiring diagram), check the gear 
motor fuse (overload protector), thermal protector, gear motor capacitor, and motor 
windings. If the gear motor starts, but the auger does not turn, check the gear motor 
coupling between the auger and the gear motor. If the compressor starts at the same 
time the gear motor starts, check the X compressor relay on the control board.
5) Freeze Cycle – "COMP", "GM" LEDs are on. The compressor and fan motor energize, 
the water control relay, gear motor, gear motor protect relay, heater control relay, and 
heater remain energized. Ice production begins 4 to 6 minutes after the compressor 
and fan motor start depending on ambient and water temperature conditions. The 
upper oat switch and lower oat switch operate the water control relay and inlet 
water valve as needed to continue the icemaking process. Diagnosis: Check that 
the compressor and fan motor are running. If not, check for voltage on and to the 
compressor (X relay on the control board). Check that the gear motor protect relay 
circuit terminals 3 and 5 are closed, check the compressor internal overload (thermal 
protector), the compressor capacitors, fan capacitor, and voltage to the fan motor.










