NOTICE
• This appliance is not intended for outdoor use.
• Normal operating ambient temperature:
– Refrigerators and Solid Door Freezers 45°F to 100°F (7°C to 38°C)
– Glass Door Freezers 45°F to 80°F (7°C to 27°C)
Operation of the appliance, for extended periods, outside of this normal
temperature range may affect appliance performance.
• The appliance must not be located next to ovens, grills, or other high heat
producing equipment.
• The appliance must not be located in a corrosive environment.
• Minimum Clearance:
Models Side Top Rear
Reach-In Refrigerators and Freezers
Except 2-Section Freezers
0" (0 cm) 0" (0 cm) 3" (8 cm)
2-Section Freezers 0" (0 cm) 10" (25 cm) 3" (8 cm)
The diagnostic procedure is a sequence check that allows you to diagnose the electrical
system and components. Before proceeding, check for correct installation and proper
voltage per nameplate. Always choose a neutral (W) to establish a good neutral
connection when checking high voltages. If the display is in alarm, see "III.D. Alarm
Safeties."
IMPORTANT
The maximum allowable voltage variation is ±10 percent of the nameplate rating.
115VAC is used as a reference voltage when checking voltage to components.
Voltage may vary depending on power supply.
1. Factory Default Settings:
a) Temperature Setpoint:
Model Auxiliary Code Temperature Setpoint
Refrigerator All 38°F (3°C)
Freezer All -2°F (-19°C)
b) Temperature Display Scale: °F.
For further details, see "II.C. Control Module Check" or "III. Controls and Adjustments."
• There is a minimum 2-min. Comp on time and 2-min. Comp off time.
1) Unplug the appliance from the electrical outlet.
2) Remove the front panel.
3) Plug the appliance back into the electrical outlet.
4) Conrm 115VAC at CM 2 (L) (BK) to neutral (W).