Owner's manual

19
2. Condensing Unit
1) Connect the wire harness wires to the appropriate terminals on the condensing unit's
terminal board using the wiring label or Fig. 8 as a reference. Be sure to connect the
ground wire (included in the wire harness).
2) Supply power from the electrical panel to the condensing unit. (This differs from KM
style installations.)
3) Connect the wire leads in the power supply junction box to the power supplied from the
disconnect or electrical panel. Connect a ground wire to the ground screw.
4) Replace all removed parts and panels in their correct positions.
5) Turn on the power supply to the condensing unit.
WARNING
1. Be sure the ground circuit for both units has been properly installed.
2. The condensing unit should have power for a minimum of 4 hours prior to
startup to prevent compressor damage.
Fig. 6
WARNING
ELECTRICAL CONNECTION
The white lead must be connected
to the neutral conductor of the power
source.
Miswiring results in severe damage to
the icemaker.
(See Fig. below.)
208-230/60/1
(3 wire with neutral for 115V)
Power Supply
Junction Box
Brown
White
Black
L1
N
L2
208-230V
115-
120V
Fig. 7