Service Manual

11
2. Prep Table: Refrigerator
Prep Table Top Sequence Flow Chart
2. Cool Down
3. Cool Down Achieved
Comp energized
ConFM energized
EvapFM energized
EvapFM energized
Comp de-energized
ConFM de-energized
4. Defrost
CTh above setpoint
CTh cools to setpoint
CTh above
setpoint
Defrost Termination:
46°F (7.7°C) achieved or
45 min. backup defrost
timer terminated.
CTh in control
1. Startup
EvapFM energized
6-hr. DT terminates
5-min. min. DT starts
45-min. max. DT starts
DH energized
Comp de-energized
ConFM de-energized
EvapFM de-energized
Defrost:
Time/Temp achieved.
Power on
Red LED On
(5 sec. Delay)
Red LED Off
Green LED Flashes
If Red LED Flashes,
check CTh or DTh
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DH-defrost heater
DT-defrost timer
DTh-defrost thermistor
EvapFM-evaporator fan motor
Note: Delays
a) 2-min. minimum Comp on timer starts when Comp energizes.
b) 2-min. minimum Comp off timer starts when Comp de-energizes.
c) 5-min. minimum defrost time.
d) 45-min. maximum defrost time.
e) DOT (drip off time) 1-min. Comp/ConFM delay timer starts when defrost termination temperature is met (drip off time (DOT)).
f) FDD (fan delay after defrost) EvapFM starts once 30-sec. EvapFM delay timer terminates or DTh reaches 40°F (4.4°C).
g) If evaporator temperature raises above 50°F (10°C) during the cooling cycle, 6-hr. DT resets.
*
2-min. Comp off
timer starts
2-min. Comp on
timer starts
Evap. Temp.
reaches 46°F (7.7°C)
DH de-energized
6-hr DT starts
After DOT Delay:
Comp energized
ConFM energized
After FDD
EvapFM energized
*
*
*
*
*
*
DTh in control
5. Defrost Termination
6-hr. DT terminates
Evap. temp. below
50°F (10°C)
Defrost
Terminated