2. SR: Refrigerator
SR - Refrigerator Sequence Flow Chart
2. Cool Down Achieved
3. Cool Down Restarts
EvapFM energized
Comp de-energized
ConFM de-energized
4. Defrost
CTh above setpoint
CTh cools to setpoint
CTh above
setpoint
Defrost Termination:
46°F (7.7°C) achieved or
45 min. backup defrost
timer terminated.
CTh in control
1. Startup/Cool Down
Comp energized
ConFM energized
EvapFM energized
5-hr. DT starts
5-hr. DT terminates
5-min. minimum DT starts
45-min. maximum DT starts
DH energized
Comp de-energized
ConFM de-energized
EvapFM de-energized
Power on
Yellow LED On
(10-sec. Delay)
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DH-defrost heater
DT-defrost timer
DTh-defrost thermistor
EvapFM-evaporator fan motor
Note:
a) 2-min. minimum Comp on timer starts when Comp energizes
b) 2-min. minimum Comp off timer starts when Comp de-energizes
c) 5-hr. cumulative compressor run-time defrost timer
d) 5-min. minimum defrost time
e) 45-min. maximum defrost time
*
Evap. Temp. achieves
46°F (7.7°C) or
45 min. DT terminates
DH de-energized
Comp energized
ConFM energized
EvapFM energized
* *
DTh in control
5. Defrost Termination
5-min. minimum and
45-min. maximum
DT starts
*
*
Red, Yellow, and
Green LEDs Cycle
Red and Green LEDs on
Yellow LED off
Green LED on
Red and Yellow LEDs off
Defrost: Time achieved.
5-hr. DT terminates
*
*